Proservo NMS5
64
Hauser
7.5.4
ENRAF Bi Phase Communication Board (COM-3) Setting
Jumper Setting
COM-3 Communication Board Jumper Setting
Communication Setting
Select "V1/ENRAF BPM" at the matrix position GVH=286.
Communication Setting
Polling address is set at GVH=285 "ADDRESS" of NMS5 matrix. The allowable range is from 00 to 99.
Caution!
A to F for polling address can not use.
Communication Setting
•
Switch S1: Reset switch
•
Connector J3: Communication port for debugging
Jumper
Function
Default Condition
JP1 (Mode)
ROM type setting
1-2 short: 27C4096
2-3 short: 27C1024
2-3 short
JP2 (Reset)
CPU mode setting (Fixed)
1-2 open
3-4 short
5-6 short
J3 (WD)
Baud rate setting
1-2 short: 1200 bps
1-2 open: 2400 bps
1-2 open