Proservo NMS5
Hauser
57
7.2
Settings for NMT 53x Connections
The following settings are required to display NMT 539 data on NMS5 screens.
Caution!
For NMT535/539/532 connections, refer to the appropriate operating manual for the device.
Item
Procedure
Remarks
Figure. 59:
Matrix Group: Service
Static Matrix
Figure. 60:
Static Matrix
1.
In Static Matrix
"MORE
FUNCTION", invoke
GVH=030 "MATRIX
OF" and select
"SERVICE".
2.
Invoke the Dynamic
Matrix GVH=362
"CONNECTION
NMT" screen.
3.
Use the "+" and "-"
keys to display
"AVERAGE" and
press "E" to set data.
4.
Press "E" to return to
"SYSTEM DATA" and
press the "-" key to
return to "MORE
FUNCTION".
5.
Invoke Static Matrix
"GVH=030 MATRIX
OF". NMS5 matrix is
divided into matrix
groups.
Select
"TEMPERATURE"
from these groups.
6.
"EDITING
ENABLED" is
displayed on the
LCD.
7.
The average liquid
temperature is
displayed on
Dynamic Matrix
screen GVH=440.
8.
The temperature of
each contact is
displayed on
Dynamic Matrix
screens GVH=450 to
GVH=459.
•
Set access code 51.
•
NMS HART connection
(terminal 24 & 25) must
have corresponding IS
input in order to
configure NMT IS
version.
•
The Static Matrix
GVH=010 "LIQUID
TEMP." screen also
displays the average
temperature.
MORE
FUNCTION
SYSTEM
DATA
CONNECTION NMT
3 6 2
MATRIX OF
0 3 0
MORE
FUNCTION
MATRIX OF
0 3 0
7 Commissioning