Proservo NMS5
106
Hauser
13
Matrix
13.1
Programming Matrix
0
123
4567
89
0
1
2
3
V
H
NMS5 Programming Matrix (Static Matrix)
GROUP MESSAGE
Display Text
Parameters,
unit, etc
Default Data
MEASURED VALUE 1
MEASURED VALUE 2
OPERATION
MORE FUNCTION
16000.00mm
MEASURED LEVEL
Display
0.0 mm
ULLAGE LEVEL
0.0°C
LIQUID TEMP.
Display
STOP
OPERATION 16000
See operation
commands below
Select (50)
CALIBRATION
MATRIX OF
Select
Display
See status table below
OPERATING STATUS
STOP
Display
DEV(1)
Display
0.0 mm
0.0 mm
UPPER INTERF. LEV.
Display
DEV(2)
Display
Display
UNBALANCED
BALANCING STATUS
Display
MIDD. INTERF. LEV
Display
Display
BOTTOM LEVEL
0.0 mm
0.0°C
GAS TEMPERATURE
LEVEL
LEVEL
OPERAT.BY NRF
Display
Display
98 627 8:21:00
CALENDER
Currect data
Display
Display
Display
Currect data
Currect data
ALARM CONTACT 0
NO ALARM
NO ALARM
LA 0 0 0 0
OPERAT. BY HOST
1.000 g/ml
UPPER DENSITY
0.000 - 3.000
Display/Set (50)
1.000 g/ml
MIDDLE DENSITY
0.000 - 3.000
DENSITY BOTTOM
1.000 g/ml
0.000 - 3.000
Display/Set (50)
Display/Set (50)
0 mm
ZERO POINT
Display
NO ERROR
DIAGNOSTIC CO 0
Currect data
Currect data
Display
Display
98 627 752 0 0
MPU:START ACT
0
ACCESS CODE
0, 50, 51, 777
Set
0
8424
DEVICE ID
SOFTWARE VERSION
Display
Display
SPAN
LENGTH UNIT
mm
16000.0 mm
0.0 mm
LEVEL DATA
Display
WATER BOTTOM
0.0 mm
Display
When new NMS status is selected at GVH=272, new status codes are showed at matrix position GVH=021 as follows;
Code
Meaning
NMS Display
Code
Meaning
NMS Display
0
1
2
3
4
5
6
7
8
9
10
.ODElNITION
Displacer at reference
Displacer hoisting up
Displacer going down
Displacer stop
Level measurement, balanced
Upp. I/F level, balanced
Midd. I/F level, balanced
Bottom meas. balanced
5PPER$ENSlNISHED
-IDDLE$ENSlNISHED
REFERENCE
UP
DOWN
STOP
LEVEL
UPPER.INTERF
.LEV
.
MIDD.INTERF
.LEV
.
BOTTOM LEVEL
UPPER DENSITY
MIDDLE DENSITY
12
13
14
15
16
17
18
19
20
21
Release over tension
Calibration activated
Seek level
Follow level
Seek Upper Density
Seek Middle Density
Seek Density Bottom
Seek Upper I/F level
Follow up. I/F level
Seek Mid. I/F level
RELE. OVER TENS.
CAL. ACTIVE
LEVEL SEEKING
LEVEL FOLLOWING
UPP
. DEN. SEEKING
MID. DEN SEEKING
BOT
. DEN. SEEKING
UPP
. INT
. SEEKING
UPP
. INT
. FOLLOWING
MID.INT
.SEEKING
-
24
25
26
27
28
29
30
31
32
Code
Meaning
NMS Display
Not initialised
Stopped at High Stop
Stopped at Low Stop
Repeatability testing
Seeking water level
W
ater level, balanced
Follow water level
Over-/Under tension,
Z-Phase, ADC error
NO INITIALIZE
UPPER STOP
LOWER STOP
REPEA
T
ABILITY
W
A
TER SEEKING
W
A
TER LEVEL
W
A
TER FOLLOWING
EMARGENCY ERROR
Operating commands
2. STOP
3. BOTTOM LEVEL
4. UPPER INTERF
. LEVE
5. MIDD. INTERF
. LEVE
6. UPPER DENSITY
7. MIDDLE DENSITY
8. DENSITY BOTTOM
9. REPEA
T
ABILITY
10.W
A
TER DIP
0. LEVEL
1. UP
+ Key
Mode (Code)
OFF
RESET ALM. DIAGNO.
0 - 8
GVH157
Service Mode = ON,
MAINTENANCE
(Modbus / HAR
T only)
11
"OTTOM$ENSlNISHED
DENSITY BOTTOM
22
23
Follow Mid. I/F level
Seek Bottom level
MID. INT
. FOLLOWING
BOTTOM SEEKING
13 Matrix