Proline Promass S 100
10
Hauser
Number of switching
cycles
Unlimited
Assignable functions
• Off
• On
• Diagnostic behavior
• Limit value
– Mass flow
– Volume flow
– Corrected volume flow
– Density
– Reference density
– Temperature
– Totalizer 1-3
• Flow direction monitoring
• Status
– Partially filled pipe detection
– Low flow cut off
The range of options increases if the measuring device has one or more
application packages.
PROFIBUS DP
Signal encoding
NRZ code
Data transfer
9.6 kBaud…12 MBaud
Modbus RS485
Physical interface
In accordance with EIA/TIA-485-A standard
Terminating resistor
• For device version used in non-hazardous areas or Zone 2/Div. 2: integrated
and can be activated via DIP switches on the transmitter electronics module
• For device version used in intrinsically safe areas: integrated and can be
activated via DIP switches on the Safety Barrier Promass 100
EtherNet/IP
Standards
In accordance with IEEE 802.3
Signal on alarm
Depending on the interface, failure information is displayed as follows:
Current output
4-20 mA
Failure mode
Selectable (as per NAMUR recommendation NE 43):
• Minimum value: 3.6 mA
• Maximum value: 22 mA
• Defined value: 3.59 to 22.5 mA
• Actual value
• Last valid value
HART
Device diagnostics
Device condition can be read out via HART Command 48