Proline Promass S 100
Hauser
25
4-20 mA HART with pulse/frequency/switch output
Device plug for signal transmission (device side)
3
2
4
1
5
A0016810
Pin
Assignment
Coding
Plug/socket
1
+
4-20 mA HART (active)
A
Socket
2
-
4-20 mA HART (active)
3
+
Pulse/frequency/switch output
(passive)
4
-
Pulse/frequency/switch output
(passive)
5
Grounding/shielding
• Recommended plug: Binder, series 763, part no. 79 3439 12 05
• When using the device in a hazardous location: Use a suitably certified plug.
PROFIBUS DP
For use in the non-hazardous area and Zone 2/Div. 2.
Device plug for signal transmission (device side)
3
2
4
1
5
A0016811
Pin
Assignment
Coding
Plug/socket
1
B
Socket
2
A
PROFIBUS DP
3
4
B
PROFIBUS DP
5
Grounding/shielding
• Recommended plug: Binder, series 763, part no. 79 4449 20 05
• When using the device in a hazardous location: Use a suitably certified plug.
MODBUS RS485
Device plug for signal transmission with supply voltage (device side), MODBUS RS485 (intrinsically
safe)
1
2
4
3
5
A0016809
Pin
Assignment
Coding
Plug/socket
1
L+
Supply voltage, intrinsically safe
A
Plug
2
A
Modbus RS485 intrinsically safe
3
B
4
L-
Supply voltage, intrinsically safe
5
Grounding/shielding
• Recommended socket: Binder, series 763, part no. 79 3439 12 05
• When using the device in a hazardous location: Use a suitably certified socket.