Proline Promag H 500 PROFIBUS DP
Commissioning
Hauser
115
Fixed current
Damping output 1 to n
Failure mode
Failure current
Parameter overview with brief description
Parameter
Prerequisite
Description
User interface /
Selection / User
entry
Factory setting
Terminal number
–
Shows the terminal numbers
used by the current output
module.
• Not used
• 24-25 (I/O 2)
• 22-23 (I/O 3)
• 20-21 (I/O 4)
–
Signal mode
–
Select the signal mode for the
current output.
• Passive
• Active
Active
Assign current output 1 to n
–
Select process variable for
current output.
• Off
• Volume flow
• Mass flow
• Corrected volume
flow
• Flow velocity
• Conductivity
• Corrected
conductivity
• Temperature
• Electronic
temperature
Volume flow
Current span
–
Select current range for
process value output and
upper/lower level for alarm
signal.
• 4...20 mA NAMUR
• 4...20 mA US
• 4...20 mA
• 0...20 mA
• Fixed current
Country-specific:
• 4...20 mA NAMUR
• 4...20 mA US
0/4 mA value
One of the following options is
selected in the
Current span
parameter (→ 115):
• 4...20 mA NAMUR
• 4...20 mA US
• 4...20 mA
• 0...20 mA
Enter 4 mA value.
Signed floating-point
number
Country-specific:
• 0 l/h
• 0 gal/min (us)
20 mA value
One of the following options is
selected in the
Current span
parameter (→ 115):
• 4...20 mA NAMUR
• 4...20 mA US
• 4...20 mA
• 0...20 mA
Enter 20 mA value.
Signed floating-point
number
Depends on country
and nominal
diameter
Fixed current
The
Fixed current
option is
selected in the
Current span
Defines the fixed output
current.
0 to 22.5 mA
22.5 mA