2.5
Rackbus RS-485 option
Wiring the bus
Up to 25 Prolevel FMC 661 transmitters can be connected to the Rackbus RS-485.
Instructions for wiring and grounding the bus are to be found in Operating Instructions
BA 134F which is delivered with Prolevel instruments having the Rackbus RS-485 option.
The Prolevel can be wired as indicated in the inset in Fig. 2.9.
Note!
•
Terminal 61 is connected internally to the PE ground terminal strip
•
The screening must be grounded and have electrical continuity throughout — read
BA 134F for grounding instructions
Bus address and
termination
Fig. 2.10 shows the configuration elements
for remote operation of the Prolevel
FMC 661. Every transmitter must have a
unique bus address:
•
Switch off power, loosen screws and
open the terminal compartment
•
Set the address at DIP-switch SW1
(Example: 2 + 8 = 10)
For the last transmitter on the bus, i.e.
furthest away from the computer:
•
Switch in the terminal resistance at
DIP-switch SW2: OFF; ON; ON; OFF
•
Close front panel, tighten screws.
A
L1
L2 (> L1)
Master
Rpull
Rt
Master
Rpull
Rt
1
OFF
ON
60 61 62
2
E
OFF
ON
OFF
ON
60 61 62
60 61 62
1
OFF
ON
60 61 62
2
E
OFF
ON
OFF
ON
60 61 62
60 61 62
B
PE
PE
Rt
150
Ω
Rt
150
Ω
PE
PE
BA142_19/20
Fig. 2.9:
Rackbus RS-485 topologies
showing setting of bus
termination resistance
Inset:
Suggestion for wiring the bus
SW1
1 2 4 8 16 32
150
Ω
392
Ω
392
Ω
+5V
(=10)
ON
OFF
ON
OFF
RS-485
[EEx ia] IIC
B DGND A
L+ L-
L1 N
1b
1a
2a
2b
- + - +
SW2
BA142_21
bus termination
switch
address switch
terminal compartment
Fig. 2.10:
DIP-switches for bus address and termination
61
PE
60
62
Dat
a
B
Data A
Screen
Note!
Chapter 2: Installation
Prolevel FMC 661
18