Value for 4 mA and
20 mA
The 4mA (V0H5) and 20 mA (V0H6) values,
default values 0% and 100%, determine
the levels at which the analogue signal
range begins and ends.
Example:
4 mA = 20%,
20 mA = 80%
#
Matrix Entry
Remarks
1
V0H5
20
4mA value, 20 %
2
-
»E«
Register entry
3
V0H6
80
20 mA value, 80%
4
-
»E«
Register entry
Note!
•
Set in calibration/linearisation units
•
When V0H3 = 0, V0H5 = 0 mA value
Output on alarm
The analogue output can be set such that
it takes on distinctive values when a fault
with alarm is detected. Depending on the
setting in V1H3/V1H8, the relays may also
follow the analogue output. The entry is
made in V0H7:
•
0 = -10% of signal range
•
1 = +110% of signal range (default)
•
2 = last value is held
Example:
Output -10 % on alarm
#
Matrix Entry
Remarks
1
V0H7 0
-10% on alarm
2
-
»E«
Register entry
The current values set on an alarm are
shown in the table
V0H3 =
Current on alarm when V0H7 =
0: (-10%)
1: (+110%)
2: hold
0: 0
…
20 mA
≤
-2 mA
≥
22.0 mA
last value
1: 4
…
20 mA
≤
-2 mA
≥
22.0 mA
last value
Caution!
•
If setting 2 is chosen, the fault recognition system on the 0/4
…
20 mA signal line is
effectively deactivated. Although the transmitter recognises a fault, i.e. the alarm
relay de-energises and the associated LED lights, the signal output to any follow-up
instrumentation appears to indicate a correct measured value.
0%
100%
V0H5
V0H6
le
v
e
l
0/4 mA
20 mA
BA142_38
Fig. 4.12:
Value for 4 mA and 20 mA, V0H5 and V0H6
t
-2
4
0
22
20
V0H7
1 = +110%
2 = hold value
mA
BA142_39
0 = -10%
alarm
Fig. 4.13:
Output on alarm, V0H7
Note!
Caution!
Prolevel FMC 661
Chapter 4: Level Measurement
Hauser
31