6.3
Simulated operating mode
This function is intended primarily for checking the correct function of the system:
•
Enter 6 at V8H0 to activate the simulation mode for level measurement
•
Enter 7 at V8H0 to activate the simulation mode for level switching
•
Enter 0 at V8H0 to terminate simulation and resume normal measurements.
When the simulation mode is activated, the alarm relay flashes (Warning E613 or E614).
The following simulations are possible:
Matrix
Entry
Simulated variable
V9H6 (V8H0 = 7)
0 = switch uncovered
100 = switch covered
External limit switch
for Liquiphant values reversed
V9H7 (V8H0 = 6)
Level
Level, current, volume
V9H8 (V8H0 = 6)
Volume
Volume, current
V9H9 (V8H0 = 6)
Current
Current
The level simulation mode takes the last measured value as default value in V9H7.
Example:
Simulation of volume
and current by entry of
level in V9H7
#
Matrix Entry
Significance
1
V8H0
6
Select simulation
2
-
»E«
Register entry
3
V9H7
e.g. 80% Enter level
4
-
»E«
Register entry
5
V9H8
**.**
Volume for level
6
V9H9
**.**
Current for level
7
V8H0
e.g. 1
Measurement mode
8
-
»E«
Register entry
Example:
Simulation of current by
entry of volume in V9H8
#
Matrix Entry
Significance
1
V8H0
6
Select simulation
2
-
»E«
Register entry
3
V9H8
e.g. 500
Volume = 500 hl
4
V9H9
**.**
Current for volume
5
V8H0
e.g. 1
Measurement mode
6
-
»E«
Register entry
Example:
Simulation of covered
external limit switch
#
Matrix Entry
Significance
1
V8H0
7
Select simulation
2
-
»E«
Register entry
3
V9H6
100
Switch covered
4
V8H0
e.g. 0
Measurement mode
5
-
»E«
Register entry
V9H7
v
o
lu
m
e
, current
m
A
level units
V9H8
current m
A
volume units
BA142_49
Fig. 6.2:
Simulation mode
Prolevel FMC 661
Chapter 6: Trouble-Shooting
Hauser
43