4) »
Dry calibration«
A dry calibration for hydrostatic sensors requires:
•
the »empty« level at which the measurement should start
•
the maximum height of the liquid column at »full« level and
•
the density of the liquid
•
the calculated offset and sensitivity of the display.
Caution!
•
The sensor constants must have been entered as per Section 4.1.
•
Check the calibration during the first filling of the tank! If your calculations are
incorrect the levels measured will be incorrect also!
Example: display in %
display for p
zero
= 0
Calculate the pressure in mbar acting at
the sensor for the desired »empty« level
and the span (»full« - »empty«):
p
mbar
= 10 x
ρ
(kg/dm
3
) x g (m/s
2
) x
∆
h (m)
For 0.45 m water, display = 0%,
For 10.45 m water, display = 100%
Span (0%
…
100%) = 10 m
•
p
zero
= 10 x 1.0 x 9.807 x 0.45
= 44.13 mbar
p
span =
10 x 1.0 x 9.807 x 10.00
= 980.7 mbar
•
Offset =
p
zero =
44.13 mbar
Sensitivity = p
span
/span = 980.7/100
9.807 mbar/%
Sensor calibration
#
Matrix
Entry
Remarks
1
V0H2
e.g. 100
Full level (100%)
2
-
»E«
Register entry
3
V3H1
e.g. 44.13 Offset in mbar
4
-
»E«
Register entry
5
V3H2
e.g. 9.807 Sensitivity mbar/%
6
-
»E«
Register entry
7
V0H0
**.**
Measured value %
The Prolevel now measures 0 at 44.13 mbar
Next step
…
Set analogue outputs and relays in %, see
p. 30
…
33.
Caution!
sensor zero, f
0
frequency (V3H5)
f (Hz)
P mbar
level
BA142_33
offset
V3H1
d
is
p
la
y
s
e
n
s
it
iv
it
y
m
b
a
r/d
ig
it
, V
3
H
2
sensor sensitivity
∆
f, S
(V3H2)
Fig. 4.7:
Offset and sensitivities for dry calibration
VH
0 0
VH
0 0
100
0
»Empty«, e.g. 0.45 m
»Full« e.g. 10.45 m
p
empty
=
ρ
x g x 0.45
e.g.
= 44.13 mbar
span =
100%
=
e
.g.
10
m
BA142_34
sensor zero
point
display
sensor
offset
Fig. 4.8:
Parameters for dry calibration, display in %
ρ
gh
Chapter 4: Level Measurement
Prolevel FMC 661