2.1
Probes and sensors
Table 2.1 lists the sensors most frequently used with the Prolevel FMC 661 transmitter.
In addition to those listed, all probes which can be used with an EC 17 Z, EC 37 Z or
EC 47 Z electronic insert can be connected to the transmitter. Installation hints can be
taken from the appropriate Technical Information Sheet.
Sensor constants
Deltapilot S hydrostatic pressure sensors and EC 37 Z/47 Z inserts are supplied with the
sensor constants zero frequency »fo« and sensitivity »
∆
f« or »S«, see Fig. 2.2. For
Deltapilot S sensors the constants depend on the measuring range, see Table 2.2. Note
these constants and enter them into fields V3H5 and V3H6 during commissioning,
Section 4.1. This dispenses with the need for a recalibration of the transmitter on
replacement of the sensor or insert.
Principle
Channel 1
Channel 2
Probe
TI sheet Insert
Probe
TI sheet Insert
Capacitance
DC 11
TI 169F
DC 16
TI 096F
DC 21
TI 208F
DC 26
TI 209F
11 322 Z
E 11.81.03
11 500 Z
TI 161F
21 211
E 10.73.18
Multicap TE, TA, E, A
TI 239, 240, 242, 243
EC 37 Z
EC 47 Z
DC 11
TI 169F
DC 16
TI 096F
DC 21
TI 208F
DC 26
TI 209F
11 450 (Z/St)
TI 197
11 961 (Z)
E 04.77.04
21 262 (Z/St)
TI 227
21 265 (Z/St)
TI 195
Multicap TE, TA, E, A
EC 17 Z
EC 16 Z
FEC 22
Hydrostatic
pressure
Deltapilot S
TI 257
DB 50, 50 L, 51, 52, 53
FEB17
FEB 17P
Not suitable
Vibration
Not suitable
Liquiphant
DL 17 Z 013154-0008
FDL 30/31/35/36
TI 185F
Soliphant
DM 90 Z
…
92 Z
TI 124F
BA042
EL 17 Z
EM 17 Z
Table 2.1:
Selection of probes suitable for
use with the Prolevel FMC 661
1
3
6
5
4
2
+
I
II
CA
(pF) C(S)(pF)
17
d4
d4 / z4
7
18
d2
d2 / z2
8
FMC 480 Z
FMC 470 Z
FMC 671 / 672 / 676 / 677 Z
HAA 420 Z
1 MHz
EC 47 Z
Ex
0,652
6,805
S
I
II
f
o
475,3 57,2
EC10015EP 8
BA142_10
sensor constants
Fig. 2.2:
Location of sensor constants on
EC 37 Z/47 Z electronic insert
and Deltapilot S DB 4x housing
Cell
type
Electronic insert FEB 17/FEB 17 P
Range
f
0
∆
f
Range
f
0
∆
f
0.1 bar
BA 0
…
100 mbar
200
10
DA -100
…
100
mbar 200
5
0.4 bar
BB 0
…
400 mbar
200
2.5
DB -400
…
400 mbar
200
1.25
1.2 bar
BC 0
…
1200 mbar
200
0.833
DC -900
…
1200 mbar
200
0.476
4.0 bar
BD 0
…
4000 mbar
200
0.25
DD -900
…
4000 mbar
200
0.204
Table 2.2:
Measuring ranges and sensor
constants of
Deltapilot S DB 5x
Prolevel FMC 661
Chapter 2: Installation
Hauser
13