Coding
Field
Selection or range
default (bold)
Display
Info
C122
Slope is displayed
100,0 %
75.0 ... 140.0 %
C123
Calibration status
is displayed
o.k.
E xxx
C124
Store calibration
results?
yes
no
new
If C123 = E xxx, then only no or
new.
If new, return to C.
If yes/no, return to »Measure-
ment«
The factory settings are printed in bold; functions printed in
italics are not available in the basic version.
100.0
C122
Slope
%
o.k.
C123
Status
yes
C124
Store
OM23FE5B.CHP
Liquisys M COM 223 F / 253 F
Instrument configuration
Hauser