Technical data
Proline Promag 51
80
Hauser
10
Technical data
10.1
Technical data at a glance
10.1.1
Application
10.1.2
Function and system design
Measuring principle
Electromagnetic flow measurement on the basis of Faraday’s Law.
Measuring system
10.1.3
Input
Measured variable
Flow rate (proportional to induced voltage)
Measuring range
Typically v = 0.01 to 10 m/s (0.033 to 33 ft/s) with the specified measuring accuracy
Operable flow range
Not in custody transfer mode: 1000 : 1
In custody transfer mode up to 160 : 1 (corresponding to 0.04 to 10 m/s)
Input signal
Status input (auxiliary input)
• Galvanically isolated
• U = 3 to 30 V DC
• Ri = 5 k
• Configurable for: totalizer reset, positive zero return, error message reset
In the custody transfer mode, error messages can only be reset and a display test function activated
via the status input!