Installation
Proline Promag 51
18
Hauser
3.2.7
Flow characteristics
Please indicate the following data in all requests and orders for devices subject to metrological
controls:
Nominal values DN or permanent flowrate Q3
This information is shown on the nameplate and must be given in the order text.
Current output / pulse output
The permanent flowrate Q3 (~10 m/s), which is set at the factory, is decisive for scaling the current
output; if required, also provide the pulse output values.
Permanent flowrate characteristics
Nominal
Diameter DN
Q1
Q2
Q3
Q4
Q3/Q1
[mm]
[m³/h]
[m³/h]
[m³/h]
[m³/h]
[m³/h]
15
0.04
0.06
6.3
7.9
160
25
0.10
0.16
16
20
160
32
0.16
0.25
25
31
160
40
0.25
0.40
40
50
160
50
0.39
0.63
63
79
160
65
0.63
1.0
100
125
160
80
1.0
1.6
160
200
160
100
1.6
2.5
250
313
160
125
2.5
4.0
400
500
160
150
3.9
6.3
630
788
160
200
6.3
10
1000
1250
160
250
10
16
1600
2000
160
300
16
25
2500
3125
160
350
16
25
2500
3125
160
400
25
40
4000
5000
160
500
39
63
6300
7875
160
600
63
100
6300
7875
100
700
63
100
6300
7875
100
800
63
100
6300
7875
100