Level Measurement at a Glance
*Can be performed in reverse order
Function
Matrix
Action
1 Reset transmitter
V9H5
●
Enter 671: »+« and »-« keys,
⇒
changes digit
Press »E« to register entry
-
Omit if commissioned as in Section 4.1
2 »Empty« calibration*
V0H1
●
Fill vessel 0
…
40% full (probe covered)
Enter level in %, m, ft, etc.
Press »E« to register entry
3 »Full« calibration*
V0H2
●
Fill vessel 60
…
100% full
Enter level in %, m, ft, etc.
Press »E« to register entry
4 0/4 mA signal
V0H3
V0H5
V0H6
●
Enter 0 for 0
…
20 mA signal, 1 for 4
…
20 mA signal
Press »E« to register entry
●
Enter level for 0/4 mA signal (if not 0)
Press »E« to register entry
●
Enter level for 20 mA signal (if not 100)
Press »E« to register entry
Silometer FMX 570
Measurement at a Glance