Installation
This Chapter describes:
•
The probes for use with the Silometer FMX 570
•
Silometer installation in a rack or Monorack housing
•
Transmitter wiring
•
Sensor connection.
•
Technical data.
Warning!
•
The Silometer FMX 570 transmitter must be installed outside explosion hazardous
areas.
2.1
Probes and sensors
Table 2.1 lists the probes most frequently used with the Silometer FMX 570 transmitter.
In addition to those listed, all probes which can be used with an EC 37 Z or EC 47 Z
electronic insert can be connected to the transmitter. Installation hints can be taken from
the appropriate Technical Information Sheet.
Sensor constants
Deltapilot S sensors and EC 37 Z/47 Z inserts for capacitance probes are supplied with
the sensor constants zero frequency »fo« and sensitivity »
∆
f« or »S«. For Deltapilot S
sensors the constants are printed on a label stuck inside the sensor head, for inserts
they are printed on the name plate, see Fig. 7.1, Section 7.3.
Note these constants and enter them into fields V3H5 and V3H6 during commissioning,
Section 4.1. This dispenses with the need for a recalibration of the transmitter on
replacement of the sensor or insert.
Principle
Probe
TI sheet
Insert
Capacitance,
Multicap
11 500 Z
TI 161F
Multicap DC 11
TI 169F
Multicap DC 16
TI 096F
Multicap DC 21
TI 208F
Multicap DC 26
TI 209F
Multicap TA
TI 239F
Multicap TE
TI 240F
Multicap E
TI 242F
Multicap A
TI 243F
EC 37 Z
EC 47 Z
FEC 12
Hydrostatic pressure
Deltapilot S
TI 031F
DB 50...53
TI 257P
FEB 17 (P)
Table 2.1:
Selection of probes suitable for
use with the Silometer FMX 570
Cell
type
Electronic insert FEB 17/FEB 17 P
Range
f
0
∆
f
Range
f
0
∆
f
0.1 bar
BA 0
…
100 mbar
200
10
DA -100
…
100 mbar
200
5
0.4 bar
BB 0
…
400 mbar
200
2.5
DB -400
…
400 mbar
200
1.25
1.2 bar
BC 0
…
1200 mbar
200
0.833
DC -900
…
1200 mbar 200
0.476
4.0 bar
BD 0
…
4000 mbar
200
0.25
DD -900
…
4000 mbar 200
0.204
Table 2.2:
Measuring ranges and sensor
constants of the
Deltapilot S DB 5x
Silometer FMX 570
Chapter 2: Installation