Manual linearization with
automatic level
registration
Step
Matrix
Entry
Significance
1
V9H5
e.g. 672
Reset transmitter (default = operating mode 1)
-
Enter sensor constants at V3H5 and V3H6
2
-
»E«
Register entry
3
V0H1/V0H2 -
Calibrate as described in e.g Section 4.2
4
V2H1
1
Select automatic entry of level
5
-
»E«
Register entry
6
V2H2
1
…
30
Enter table entry number
7
-
»E«
Register entry
8
V2H3
e.g. 0
Fill vessel, enter volume in required units
9
-
»E«
Register entry
10
V2H4
-
Select level entry field
11
-
»E«
Press »E« to write measured level in matrix
12
V2H5
2
…
30
Enter next table entry number
13
-
»E«
Register entry
-
The system jumps to V2H3, V2H2 is incremented
14
V2H3
Repeat steps 8 to 13 until all points are entered
15
V2H0
3
Select manual linearization table
16
-
»E«
Press »E« to activate linearization
Note!
•
For this procedure the tank can be filled for calibration then emptied for linearization.
•
If a volume calibration is performed, Section 4.3, then the value displayed at field
V2H4 is a »volume« not a level.
•
Set analogue output in same units as used for linearization
Corrections to manual
linearization
An incorrect entry can be overwritten by selecting the appropriate table number at V2H2
and entering the new value at V2H3 or V2H4.
•
If 9999 is entered, the entire point is deleted from the characteristic.
•
On activation the linearization is resorted and subjected to a plausibility check.
Step
Matrix
Entry
Significance
1
V2H2
1
…
30
Enter table entry number where correction is to be made
2
-
»E«
Register entry
3
V2H3/H4
e.g. 10
Correct volume or level
4
-
»E«
Register entry
5
-
Make further correction as in steps 1 to 4
6
V2H0
3
Select manual linearization table
7
-
»E«
Press »E« to activate linearization
Chapter 5: Linearization
Silometer FMX 570
28