Operating Instructions

Fieldgate FXA320

Ethernet, Modem and GSM gateway for 4 – 20 mA analog 
and binary devices

Summary of Contents for Fieldgate FXA320

Page 1: ...BA00053S 00 EN 16 15 Version 1 07 xx 71282724 Operating Instructions Fieldgate FXA320 Ethernet Modem and GSM gateway for 4 20 mA analog and binary devices ...

Page 2: ...Fieldgate FXA320 0 Endress Hauser TAG No XXX000 Ser No X000X000000 Order code 00X00 XXXX0XX0XXX www endress com deviceviewer Endress Hauser Operations App Serial number ...

Page 3: ... 4 20 mA device 22 4 2 4 Loop powered 4 20 mA device 22 4 2 5 Switching device binary input 23 4 3 Network connection 24 4 3 1 Fieldgate Analog 24 4 3 2 Fieldgate Ethernet 24 4 3 3 Fieldgate GSM 24 5 Commissioning 25 5 1 Establishing communication via service interface 26 5 1 1 Connect the Fieldgate 26 5 1 2 Set up a standard 9600 bps modem 26 5 1 3 Check the modem properties 28 5 1 4 Set up the d...

Page 4: ...82 7 4 1 Autorefresh 82 7 4 2 Refresh 82 7 4 3 Endress Hauser 82 8 Advanced Functions 83 8 1 XML data 83 8 1 1 Generating the XML Data 83 8 1 2 Evaluating the XML data 83 8 2 Historical data 84 8 2 1 Calling up the historical data 84 8 2 2 Interpreting the historical data 85 8 3 Wireless Application Protocol WAP pages 86 8 3 1 Connecting to the WAP homepage 86 8 3 2 WAP pages 86 8 4 SupplyCare 87 ...

Page 5: ...xx BA282F 00 en 08 05 Unknown No Revision Index 1 03 xx NA Bug fixes Customer specific software update 1 04 xx NA Bug fixes Customer specific software update 1 05 xx BA053S 04 en 09 08 Restructuring of manual Manual not released due to pending Version 1 06 xx 1 06 xx BA053S 04 en 01 09 Various menus Addition of new control parameters Overview page Redesign of measurement presentation 1 07 xx BA000...

Page 6: ...Fieldgate FXA320 Endress Hauser 4 ...

Page 7: ...sioning and operation Fieldgate FXA320 must be installed connected operated and maintained according to the instructions in this manual personnel must be authorised and suitably qualified 1 4 Operational safety The unit may only be operated under the permissible ambient conditions given in the technical data Explosion hazardous areas Fieldgate FXA320 itself may not be mounted in explosion hazardou...

Page 8: ...re of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected To ensure that the unit complies with current FCC regulations and safety requirements limiting both maximum RF output power and human exposure to radio frequency ra...

Page 9: ...Keys buttons program icons tabs menus commands Start Programs Endress Hauser or Enter Select Print in the File menu CAPS Details on paths and file names in the text DOKUFMR2XX PDF or WIN HLP Angle brackets Variables CD ROM drive Icon Meaning DANGER This symbol alerts you to a dangerous situation Failure to avoid this situation will result in serious or fatal injury WARNING This symbol alerts you t...

Page 10: ...used in drawings to indicate if necessary non explosion hazardous areas Devices located in safe areas still require a certificate if their outputs run into explosion hazardous areas Icon Meaning Direct voltage A terminal to which or from which a direct current or voltage may be applied or supplied Alternating voltage A terminal to which or from which an alternating sine wave current or voltage may...

Page 11: ... Special version Modem Interface 1 2 4 9 Ethernet Analogue modem GSM modem without antenna Special version DAT Module A B Y without DAT module with DAT module Special version Input A B 2 analog input 2 analog input and 4 binary inputs Contact rating Ser No Kom No Dat Insp Made in Germany 79689 Maulburg 0 C Tamb 60 C 0 C Tamb 50 C Anreihmont age row mounting FIELDGATE FXA320 SIL TI 369F 15 16 1 2 L...

Page 12: ...cumentation NOTE All devices are shipped with Brief Operating Instructions These Brief Operating Instructions do not replace the associated Operating Instructions Detailed information on the device can be found in the Operating Instructions and in the other documentation Available for all device versions via Internet www endress com deviceviewer Smartfone Tablet Endress Hauser Operations App The i...

Page 13: ...tore and for iPhones and iPads App Store Via the serial number 1 Launch the Endress Hauser Operations App 2 Enter the serial number Ser no of the device see nameplate All the associated documentation is displayed Via the 2 D matrix code QR code 1 Launch the Endress Hauser Operations App 2 Scan the 2 D matrix code QR code on the nameplate All the associated documentation is displayed ...

Page 14: ...mits to be configured and if required automatically activates the next delivery The options here range from a simple purchasing requisition via e mail through to fully automatic order administration when XML data is coupled into the planning systems on both sides Fig 3 1 Inventory Management using Fieldgate FXA320 Fig 3 2 shows a typical configuration when Fieldgate FXA320 FXA520 is used with Supp...

Page 15: ...e PC can communicate with the device at any one time In this configuration the Fieldgate has to be selected before each access so that it is ready for online operation The Windows internal telecommunications network can be used for dialling After this the Fieldgate can be accessed with a standard web browser Fieldgate can also dial itself into a central server e g in order to deliver periodic meas...

Page 16: ... into packets which can be sent depending on requirement and capacity Data transmission in packets enables not only greater transmission rates but also permanent dial in operation The Fieldgate is thus permanently in a position to connect to the Internet an Intranet or a mailbox whereby data are only transferred as required e g if a new e mail is sent or a new Internet page is called up In this ca...

Page 17: ...tus L signal 3 5 V H signal 15 30 V Inputs 1 3 event counting measuring range 0 12 5 kHz Inputs 2 4 frequency measurement 4 7 Hz 1 12 5 kHz 4 The input channel is configured using the Fieldgate Web server 3 3 3 Relay output The relay can be used to signal an alarm or save power Alarm relay The relay is configured as an alarm relay by not selecting the function Power Down Devices between Scan Cycle...

Page 18: ...icates a fault Red LED flashes Indicates a warning on site communication via PC hardware is unlocked system start 3 Yellow LED Switching status of the built in relay LED off relay de energised LED on relay energised 4 Yellow LED Indicates connection active 5 Yellow LED Indicates communication GSM version field strength display if no connection Item Element Meaning 6 Switch for Channels 1 and 2 act...

Page 19: ...led and linearized in the Fieldgate Web server Fig 3 7 System architecture for 4 20 mA connections 3 5 2 Binary input Fieldgate FXA 320 can be optionally equipped with four binary inputs to connect e g level switches Fig 3 8 System architecture for FXZ520 analog and digital input modules 4 20 mA 4 20 mA Fieldgate FXA320 Fieldgate FXA320 ENDRESS HAUSER RN221N ENDRESS HAUSER RN221N Analog Ethernet G...

Page 20: ...nsions MS Internet Explorer 5 0 with current security updates Netscape Navigator 4 7 with current security updates Opera 6 0 with current security updates Mozilla Firefox 1 0 with current security updates Operating system Service Pack extensions Windows 2000 SP 1 or higher Windows XP Home Professional Add on Version Function SupplyCare 1 00 xx Inventory Control program ...

Page 21: ... connected to a common power supply Fieldgate units connected to an Ex power supply and Fieldgate units connected to Non Ex power supply must have a lateral clearance of 50 mm 2 Fig 4 1 Dimensions of Fieldgate FXA320 GSM version For the GSM version it is also important that there is good reception from the mobile communication network at the location at which the unit is mounted It may be necessar...

Page 22: ...l forwards until it is detached from its fastening 2 Pull the panel downwards to access the connections 3 Close the panel after use Fig 4 3 Opening the front panel 4 1 4 Dismounting a Fieldgate Dismounting 1 Switch off the power to the Fieldgate 2 Insert a screwdriver blade between the terminal block and the housing and prise the block from its socket Repeat for all terminal blocks 3 Insert the sc...

Page 23: ...d at installation Fig 4 5 Wiring up of power supply and relay Location No Function Remarks 1 1 Power L L1 Depending on device type see nameplate on side 20 60 VDC 20 30 VAC 85 253 VAC 50 60 Hz 10 30 VDC 2 Power L N 7 CH 1 Externally powered 4 20 mA device 8 9 CH 1 Loop powered 4 20 mA device 10 11 CH 2 Externally powered 4 20 mA device 12 13 CH 2 Loop powered 4 20 mA device 14 15 NC relay Max 253 ...

Page 24: ...tch setting and connections are as shown in Fig 4 7 Fig 4 7 Wiring and switch setting for loop powered 4 20 mA devices Fieldgate FXA 320 Micropilot S Sensor 2 Sensor 1 7 11 8 12 CH 1 CH 2 Switch setting located behind front panel externally powered e g 4 wire passive current output active Fieldgate FXA 320 Micropilot M Prosonic M Levelflex M Sensor 2 Sensor 1 9 13 10 14 CH 1 CH 2 Switch setting lo...

Page 25: ...an be connected as shown in Fig 4 8 Limiting values for the input signals DC PNP are Low signal 0 3 VDC to 5 VDC High signal 1 15 VDC to 30 VDC Fig 4 8 Wiring of optional binary inputs GND1 GND2 B2 B4 B1 B3 23 27 24 28 22 26 Fieldgate FXA 320 Minicap DC PNP Nivector DC PNP Soliphant DC PNP Liquiphant DC PNP 24 VDC e g L signal 3V 5V H signal 15V 30V Binary inputs B1 B4 ...

Page 26: ...t is recommended that a switch is used in preference to a hub Fig 4 10 Connection of Fieldgate to an Ethernet network 4 3 3 Fieldgate GSM Fieldgate requires an GSM external antenna which can be purchased from Endress Hauser as an accessory The antenna cable plugs into the socket on the front of Fieldgate and must be mounted outside of any control cabinet or field housing In areas of poor GSM recep...

Page 27: ...dgate is always commissioned via the service interface The chapter is structured as follows Chapter 5 1 describes the steps necessary to establish connection via the service interface Chapters 5 2 to 5 4 describe the individual steps required to set up communication with the Ethernet Modem and GSM versions of the Fieldgate respectively Chapter 5 5 describes the setup of other communication facilit...

Page 28: ...n female connector To connect the Fieldgate to your computer 1 Plug the 9 pin connector into the COM port RS 232C of your computer 2 Plug the 3 pin connector in the service port of the Fieldgate This is located behind the front panel see chap 4 1 3 5 1 2 Set up a standard 9600 bps modem Now set up a standard 9600 bps modem on your computer 1 Select Start Settings Control Panel Telephone and Modem ...

Page 29: ...dem Options dialog If the Standard 9600 bps Modem is in the list go to Chapter 5 1 3 Otherwise press Add see below 4 The Install New Modem wizard starts Tick the Don t detect modem checkbox and press Next to continue 5 Now select the Standard 9600 bps Modem from the list and press Next to continue ...

Page 30: ... modem and press Next to continue 7 When the modem has been successfully installed press Finish to close the wizard 8 The Standard 9600 bps Modem is now in the modem list 5 1 3 Check the modem properties 1 In the Phone and Modem Options Modems dialog select Standard 9600 bps Modem and press Properties ...

Page 31: ...ed tab 3 Press the Change Default Preferences button Set the Flow Control parameter to None 4 Select the Advanced tab Check that Data bits 8 Parity None and Stops bits 1 Press OK to confirm any changes made in the settings and to close the dialog 5 Close the remaining dialog boxes by pressing OK ...

Page 32: ... Now set up the dial up connection 1 Select Start Settings Control Panel Network Connections 2 The Network Connection dialog opens Double click on New Connection Wizard 3 The New Connection Wizard opens press Next to continue 4 Select the option Connect to Internet press Next to continue ...

Page 33: ...ss Next to continue 6 Select the option Connect using a dial up modem press Next to continue 7 If a more than one modem is available on the computer you will be asked to select the one to be used for the connection from the Select a Device dialog Make sure the correct one is ticked Press Next to continue ...

Page 34: ...ress Hauser 32 8 Enter the name of the connection e g Fieldgate Service Adapter press Next to continue 9 Enter 0 as phone number to dial press Next to continue 10 Select the connection availability e g Anyone s use press Next to continue ...

Page 35: ...account name Do not select the options Make this the default Internet Connection Turn on Internet Connection Firewall Press Next to continue 12 Select the option Add a shortcut and press Finish to create the connection and close the wizard An icon is added to the desktop The connection is added to the Network Connections folder 13 The Connect Fieldgate Service Adapter dialog appears Press Cancel t...

Page 36: ...etwork Connections dialog right click on Fieldgate Service Adapter and select the Properties menu 2 In Fieldgate Service Adapter Properties dialog press the Configure button The Modem Configuration dialog appears Deselect the option Enable Flow Control press OK to close the dialog Press OK to close the Fieldgate Service Adapter Properties dialog 3 Now double click on the Fieldgate Service Adapter ...

Page 37: ...n then the Networking tab Now select Internet Protocol TCP IP and press Properties 6 In the Properties dialog that now appears press the Advanced button the dialog Advanced Properties opens at the General tab Deactivate the Use default gateway on remote network option press OK Close all dialogs with the exception of Connect ...

Page 38: ...n the Fieldgate Web Server 10 The Fieldgate entry page appears in the browser You are registered with administrator rights and can now set up the Fieldgate communication parameters see chap 5 2 to chap 5 5 5 1 6 Securing changes made via the service interface 1 When Fieldgate has been configured Select Settings Special to restart the system and register the changes In the System Restart dialog che...

Page 39: ...been deleted for security reasons Parameter Example Your value Description Host name MyFieldgate Symbolic name string of the Fieldgate in the DHCP server Required for BootP and DHCP server only This must be allocated by your network administrator and be present on the DHCP server before it can be used IP Assignment Manual BootP Protocol DHCP Way in which the IP address is assigned to the Fieldgate...

Page 40: ...ly stored 5 When the restart is complete close the web server unplug the service connector and switch off the Fieldgate Close the front panel 6 Plug in the Ethernet connector and switch on the Fieldgate Connect the Fieldgate via the host computer as described in chap 5 2 3 5 2 3 Connect to Fieldgate via Ethernet If Fieldgate has been allocated a fixed IP address your computer must have an IP addre...

Page 41: ... dial up computer default 192 168 254 2 Router address if used otherwise leave default address Additional AT commands For Service only no entry required Parameter Example Description ISP Phone Number Dial in number of Internet Service Provider ISP User Name User Name provided by Internet Service Provider ISP Password Password provided by Internet Service Provider ISP DNS1 IP address of the Domain ...

Page 42: ...to the Fieldgate 3 Now configure any other communication parameters e g e mails as described in chap 5 5 4 You may now wish to configure additional Fieldgate device functions e g limit values scanning cycle in the Fieldgate Web server as described in Chapter 6 5 When configuration is complete select Settings Special to restart the system and register the changes 6 In the System Restart dialog chec...

Page 43: ... modem In the Connection Name dialog enter e g Fieldgate Analog Connection In the Number to Connect dialog enter the phone number of the Fieldgate All other settings are identical 2 In the Network Connections dialog Start Settings Network Connections right click on the new connection e g Fieldgate Analog Connection and select Properties The Properties dialog opens 3 Select the modem used with the ...

Page 44: ...ctions dialog double click on e g Fieldgate Analog Connection or click on the icon on your desktop the Connect dialog appears Click the Dial button to make the connection 2 Open your Internet Browser enter the default Fieldgate address http 192 168 254 1 then press Enter 3 The Connect to dialog appears Enter the User Name super if not changed during set up Enter the Password super if not changed d...

Page 45: ...utomatically searches for provider Manual Fieldgate uses provider configured in dialog IP Address Fieldgate on Dial In IP address of the Fieldgate default 192 168 254 1 Leave default address unless your PC modem does not accept this address range IP Address assigned to Dial In Peer IP address of caller default 192 168 254 2 Router address if used otherwise leave default address Parameter Your valu...

Page 46: ...ate see Table 5 5 The screenshot above is an example for Orange CH Press Send to download the parameters to the Fieldgate Do not activate GPRS Dial In Permanently until you have tested the connection 3 If you want to use a dynamic DNS server scroll down to the DynDNS Setup dialog for more information on Dynamic DNS servers see chap 8 5 Enter the parameters as appropriate see Table 5 6 Example for ...

Page 47: ...GSM provider supports CSD Before you set up the dial up connection make sure that the GSM parameters have been configured as described in Chapter 5 4 2 1 Start the New Connection Wizard and follow the procedure in chap 5 1 4 In the Select a Device dialog select the analog or GSM modem In the Connection Name dialog enter e g Fieldgate GSM Connection In the Number to Connect dialog enter the phone n...

Page 48: ...s Enter 3 The Connect to dialog appears Enter the User Name super if not changed during set up Enter the Password super if not changed during set up Press OK to register the entries and open the Fieldgate Web Server 4 The Fieldgate entry page appears in the browser You are registered with the rights associated with your user name 5 4 5 Connect via GPRS to Fieldgate In order to connect your Interne...

Page 49: ... the setting with Send Time server setup Parameter Description Time Server Enter the IP address of the time server here Protocol Set the protocol used by the time server here manual Manual time setting timing is restarted with settings entered in manual Timestamp The time server operator can tell you the protocol the server uses Periodic Fetch Enter the time interval after which the internal clock...

Page 50: ...n Proxy Server Enter IP address of proxy server Port Number proxy Server Enter port number of proxy server 8080 is standard http Proxy Server Username If the proxy server demands authentification enter the user name here Proxy Server Password If the proxy server demands authentification enter the password here Port Number Web Server Enter port number of Fieldgate s embedded web server 80 is standa...

Page 51: ...rameter Description Periodic Measurement Messages Select period for sending measurement messages from drop down menu Remind pre Boot Limit Alarms Check this box to stop the Fieldgate sending measurement mails when it is restarted after being powered down Message assigned IP Address Check this box to send the assigned IP address of the DHCP server as a information to the alarm receiver Additional T...

Page 52: ... Password If authentication is required for the specified SMTP Gateway enter the password here Leave blank if no authentication is requested or no SMTP Gateway is used Sender Address Enter the sender address of the Fieldgate here e g fieldgate company co uk With some providers the e mail address of the account holder must be specified as the sender address No mails will be accepted from other send...

Page 53: ... press Switch to Administrator Mode Settings Message Scroll down to reveal the Mail Setup page Enter your settings and confirm with Send Field Information Server FIS Setup Parameter Description Enable FIS Check this box to activate the FIS functionality of the Fieldgate FIS URL Enter the IP address or the URL of the FIS FIS Phonenumber The field appears only for the GSM version of the Fieldgate En...

Page 54: ...down the menu to reveal the SMS Setup page Enter your settings and confirm with Send SMS setup Parameter Description Enable SMS send Check the box to enable the SMS function SMS Phonenumber 1 Enter the phone number of a first person to be contacted International telephone number are to be entered as e g 33 SMS Phonenumber 2 Enter the phone number of a second person to be contacted International te...

Page 55: ...rds Table 6 1 lists the user roles with passwords that are currently available in the Fieldgate Security Setup chap 6 3 2 provides more information on setting up passwords etc Table 6 1 Fieldgate user roles and rights NOTE To avoid unauthorized access to the Fieldgate we recommend that the user names and passwords are changed during commissioning 6 1 1 Disconnecting To exit the web browser simply ...

Page 56: ...is means that the build up of the overview can be slow The user interface consists of the following elements Menu bar belongs to the web browser installed Navigation bar Settings pages 6 2 1 Menu bar Example of how the menu bar is displayed in MS Internet Explorer The IP address of the Fieldgate is entered in the address field of the Internet web browser NOTE The menu bar contains the standard fun...

Page 57: ...rator Mode You must enter user name and password if did not log on with administrator rights Settings Displays information on Fieldgate location and hardware Location shows Fieldgate location information User allows you to change your password Input allows the device web settings to be viewed Info displays various Fieldgate logs Function Description AutoRefresh No function in Administrative Mode R...

Page 58: ...e and when prompted by entering the corresponding password see chap 6 1 User Mode In User Mode Settings provides read only views of the Fieldgate location input settings and information logs which are displayed by pressing the appropriate menu The Password menu allows you to change your user password see chap 6 3 2 Administrator Mode In Administrator Mode Settings allows you to change the configur...

Page 59: ...ieldgate Fieldgate location parameters Table 6 4 Fieldgate location parameters Parameter Description Fieldgate Identification Enter the name of the Fieldgate e g FXA320 This is also displayed on the overview page in the header of your browser in the XML file and the header of the e mail Note The following characters are permitted for the Fieldgate identification name of Fieldgate Letters a z and A...

Page 60: ...p dialog appears 3 Enter the parameters you require their significance is described in the table below 4 Press Send to download the user parameters to the Fieldgate User Setup parameters Table 6 5 Significance of User Setup parameters Parameter Description Username Enter a user name max 8 characters no umlauts no special characters Password Enter a password for user name max 8 characters no umlaut...

Page 61: ...tings Chapter 5 6 Mail settings The functions offered are tailored to the Fieldgate version Table 6 6 gives an overview together with the exact location of the setup description Table 6 6 Setup pages as a function of Fieldgate communication interface Setup Function Fieldgate Ethernet Fieldgate Analog Fieldgate GSM Chapter Ethernet x 5 2 5 2 1 5 2 2 Modem x 5 3 5 3 1 5 3 2 Dialup x x 5 3 5 3 1 5 3 ...

Page 62: ...ecords see chap 8 2 Parameter Description Device Scan Cycle Time Set a scan time from continuous to 1 day from the drop down menu Settings other then continuous are required only by battery or solar powered Fieldgates Use e mail log cycle if a scan is to be made on e mail or logging events only Device Power Up Time Set a value determined by the slowest device between 2 s and 5 min default 20 s fro...

Page 63: ... assign engineering units to connected 4 20 mA devices where appropriate scale and assign engineering units to connected binary inputs assign explanatory text to connected binary devices set up the e mail response to sensor errors 1 If not already selected press Switch to Administrator Mode and log in as administrator 2 Press Settings then Input the FXA320 Inputs and Internal Sensors dialog appear...

Page 64: ... and search for the configuration file cgi Name must start with 520 If restore cgi is enter red manually in the browser the default page is uploaded Overview Page with User Rights 2 After a click on Send the corresponding configuration file is uploaded Other functions Scrolling down the reveals the following additional dialogs Parameter Description Export User Settings Click on the check box to do...

Page 65: ...ldgate A full description is to be found in chap 7 3 4 Modem Log records all transactions with the modem System Log records all Fieldgate events e g e mails sent time fetched sensor data changed Error Log records all device errors The logs can be cleared by clicking the appropriate box in the Clear Log Information dialog and pressing Send see chap 6 3 6 Special ...

Page 66: ...l and analog inputs in the appropriate setup and for Fieldgate board temperature and 5V supply in a separate Tag Setup dialog 6 4 1 Opening the setup dialogs The setup dialogue can be opened by clicking on the device tag in the Overview page when in Administrator mode or through the Settings menu as follows Procedure 1 If not already selected press Switch to Administrator Mode and log in as admini...

Page 67: ...values in engineering units corresponding to the 4 mA and 20 mA signal Units After Linearization Enter the engineering units in plain text to be used after linearization Linearization Table Enter a linearization table with maximum 16 value pairs in the form xx xx yy yy The first and last values should correspond to the lower and upper range value The X values must increase monotonically if an X va...

Page 68: ...very 10 minutes in the non volatile memory If the system is restarted between two save periods e g due to a power outage etc totalized count values can be lost in this period Frequency input Inputs 2 and 4 may be configured as frequency inputs with a frequency range 4 7 Hz 1 to 12 5 kHz 4 Input frequencies below 4 7 Hz are taken as 0 Hz Parameter Description Tag Enter the Device Tag that is to app...

Page 69: ...Hysteresis The hysteresis function allows a band to be placed below the HI or HI HI limit or above the LO or LO LO limit which delays the status change to RESET after a a limit has been violated This is used to stop the limits from triggering for example when the surface of the liquid in the tank is turbulent Fig 6 2 shows the effect for a hysteresis of 5 on a HI limit of 80 and a low limit of 15 ...

Page 70: ... moves below the low limit LL Low low alarm an alarm is set when the measured value moves below the low low limit The status is flagged in the Limit Status column If no value is entered the limit is disabled Hysteresis limit Gradient limit Sets a hysteresis band in percent of set range and a rate of change limit in absolute units The hysteresis is set below HH and H limits and above L and LL limit...

Page 71: ...aviour of analog device status and limit status for measured values outside range limits The sensor error setup dialog for both analog and digital inputs is shown below The significance of the parameters is described in Table 6 12 Sensor error setup Table 6 12 Sensor error parameters Output signal 3 6 mA or 21 mA NAMUR limits 3 6 mA to 3 8 mA 21 5 mA to 21 mA Device Status ERROR WARNING Response A...

Page 72: ...Lock then press Send The hardware lock is now enabled 6 5 2 Deactivating the hardware lock NOTE The service interface is not affected by the hardware lock and can always be used to access the Fieldgate The lock cannot be deactivated when the Fieldgate is booting this causes a device reset The lock can be deactivated temporarily by pressing the reset button for 1 second see chap 9 2 This allows acc...

Page 73: ...Logging on Procedure 1 Enter the Fieldgate IP address or domain name in your web browser After connection has been made you will be asked to log on 2 Enter your user name and the password 3 Fieldgate opens in User Mode and displays the Overview page 4 You can now view the information you require by pressing the appropriate menu Details are to be found in the chapters that follow ...

Page 74: ...from analog digital input setup page Press the Tag to view the setup and device details Description Description read from setup page Current Value Current measured value together with time stamp of scan if the time is set Status Current device or limit status together with time stamp of last status change OK device is operating correctly WARNING device is operating out of range ERROR device is ope...

Page 75: ...0 chap 6 4 4 for details of the parameters Analog input setup This dialog shows the settings for the selected device See table 6 7 chap 6 4 2 for details of the parameters Digital input setup This dialog shows the settings for the selected device See table 6 8 chap 6 4 3 for details of the parameters Sensor error setup This dialog shows the settings for error e mails See table 6 12 chap 6 4 5 for ...

Page 76: ...le 7 2 Dynamic parameters and status XML data Press XML Data in the footer of the line to generate an XML file of all the data on the page see chap 8 2 Parameter Description PV Loop Current 4 20 mA current value set for device PV of Range Measured value as a percentage of the measuring range set in device Status Simple device status according to HART specification plus 2 bytes hex information Erro...

Page 77: ...able 7 3 Significance of change password parameters 7 3 3 Input Press Input to view the devices connected to the Fieldgate Press the Tag to view the setup and device details A typical dialog is shown below more details are to be found in chap 6 4 and chap 7 2 Parameter Description User Name Enter your user name max 8 characters Password Enter your current password max 8 characters New Password Ent...

Page 78: ...uration page Parameter Description General Fieldgate order code Hardware Version Fieldgate hardware version number Firmware Version Fieldgate firmware version number OS Version Version of the operating system used Software Checksum Software checksum is used during a firmware download to check whether the transmission has been made without error Serial No Fieldgate serial number IMEI number GSM Int...

Page 79: ...nternet The internal clock has been adjusted accordingly time switching to time zone Automatic adjustment of the time server to a different time zone The parameter Time Offset related to UTC under Settings Network Time Server Setup was automtically adjusted by the time server as a result of a change in Timezone Setting valid for http time service User user changed password from ip addr A user has ...

Page 80: ...Command parameter not implemented 550 Requested action not taken mailbox unavailable E g mailbox not found no access 551 User not local please try forward path 552 Requested mail action aborted exceeded storage allocation 553 Requested action not taken mailbox name not allowed E g mailbox syntax incorrect 554 Transaction failed email ok for 1st 2nd recipient service alarm limit alarm measurement T...

Page 81: ...ider DynDns failed The Fieldgate could not transmit its IP address to a dynamic domain name server This message can occur when there are syntax errors in the Get DynDns URL entry see chap 8 5 or when the server malfunctions DynDns ok IP address of Fieldgate successfully transmitted to DynDns The message appears only after a previous DynDns failure connection to FIS failed cannot start encryption E...

Page 82: ...SM The GSM module does not have any reception signal Pin Ok GSM SIM Pin is OK User defined AT at cmd Modem GSM User defined AT commando output FAILED timeout Modem GSM Command at modem triggered a timeout FAILED modem response Modem GSM Command at modem returned an unexpected response OK modem response Modem GSM Command at modem returned an expected response GSM operator operator signal signal str...

Page 83: ...tes for an incoming call To build up a data call a second call must be made see chap 5 4 2 Auto detection of available GSM bands GSM Indicates automatically available GSM bands band MHz ok GSM Indicates which GSM Band has been selected connection to test server failed or invalid test server GSM Connection could not be made to test server In this case the GPRS connection is made again Possible reas...

Page 84: ...g Refresh causes the page display to be updated and has the same function ad the Refresh button in your Internet browser 1 Click on Refresh to activate updating The Refresh function can also be used to automatically update the page display at set the time intervals For example to refresh the page every 5 minutes 300 s enter the following in your browser http 192 168 252 1 refresh 300 7 4 3 Endress...

Page 85: ...aded to your computer for use in Office or other applications 8 1 1 Generating the XML Data 1 Press XML The parameters are downloaded into a separate page from where they can be copied and pasted 2 Note the web address this can then be accessed by your browser as a read only page no values can be changed without prior login to the Fieldgate 8 1 2 Evaluating the XML data The significance of the dat...

Page 86: ...il User ID By adding a user ID ID 1 to ID 9 to the query e g history xml ID 2 an individual view of the historical data can be obtained Fieldgate maintains pointers for each User ID indicating the time when the last query was made Only data records from this time onwards are presented Number of records The number of historical records held by Fieldgate is dependent upon the device version With dig...

Page 87: ...e e g fieldgate ser 470009010A0 tag E H Weather Station Brombach type history rev_xml 1 0 rev_xml time 20060606 081946 time timezone 120 timezone ff_version FXA320 dev 20060602 124025 ff_version os_version 3 19 os_version conf FXA320 AG4AB conf This is followed by the data for each device comprising device identifier timestamp and measured value s device id 110f191fc3 vtime 20060604 030026 vtime v...

Page 88: ...has a public IP address The IP address or domain must be known if necessary by using DynDNS see chap 8 5 8 3 1 Connecting to the WAP homepage Open the WAP homepage for the Fieldgate use your mobile phone s WAP browser The access address URL is composed as follows http IP address or Domain Name index wml Example http www fieldgate de index wml or http 212 227 127 81 index wml 8 3 2 WAP pages The WA...

Page 89: ...nd transmission technology installed on site the current inventories are recorded and transmitted to SupplyCare With SupplyCare you have a constant overview of all the current inventories Critical levels are clearly indicated and you can also receive active information on these levels if required Calculated prognosis gives additional security for replenishment planning Further information on insta...

Page 90: ... account how to set it up and how to add the information to Fieldgate The DNS server provider is www dyndns org Procedure 1 Enter the URL of your dynamic DNS server in your Internet browser e g www dyndns org 2 Press the Account button 3 Select the Create Account menu and fill out the required information Enter a username e mail address and password Agree to the licence conditions When complete pr...

Page 91: ...tton The Hostname Created dialog appears to confirm the action 7 On completion you have something like the following username e g johnsmith password e g myfieldgate hostname e g fieldgate365 ath cx 8 Now create the DynDNS string for your Fieldgate one line username password members dyndns org nic update system dyndns hostname hostname myip for the example above johnsmith myfieldgate members dyndns...

Page 92: ...way Delete all values for Limit Settings where no e mail should be sent Fieldgate receives no IP address from a DHCP Server Fieldgate is set to support the wrong protocol e g BOOTP Change the protocol setting Changes made via the Service Interface are not in Fieldgate after the next power up As long as the Service Cable is connected configuration data cannot be stored to the EEPROM Ensure persiste...

Page 93: ... button This takes approx 10 s It takes approx 30 s if a firmware update was carried out Time frame No Time frame Red LED Function release button 1 0 5 Flashes at approx 5 Hz The data of the internal EEPROM is first checked the configuration data is copied from the internal EEPROM to the DAT module 2 5 10 Off No function when released 3 10 15 Flashes at approx 2 5 Hz Configuration is reset to the ...

Page 94: ...proceed with point 3 No check the cable or connection to Fieldgate and PC Network 3 Open the DOS prompt Start Run cmd 4 Enter ping 192 168 252 1 Do you get the answer 192 168 252 1 Bytes 32 Yes The connection is OK Check your browser settings If a proxy server is used try to bypass the IP address 192 168 252 1 No There is no connection to the Fieldgate 5 Check if Fieldgate s IP and Subnet mask are...

Page 95: ...ou require see Table 9 1 below then press Send to start the download 4 The Fieldgate is rebooted after the firmware update Parameters Table 9 1 Firmware Update parameters Parameter Description Download Address Fieldgate Firmware http address at which the firmware is stored The address will be supplied to you by your Endress Hauser service center Download now Check this box to download the firmware...

Page 96: ...ngth 5 m 52014031 Triband antenna Triband flat antenna for GSM communications 52018396 Quadband antenna Dual band station antenna for GSM communications 71059393 Fieldgate Solutions Special solutions including cabinet for inventory control On request Product Description Order Code Power supply units RMA422 Multifunctional 1 2 channel top hat rail device with intrinsically safe current inputs and t...

Page 97: ...sion 1 5 W to 4 W depending upon version Dimensions W x H x D 45 mm x 108 mm x 112 mm 1 8 x 4 25 x 4 4 Mounting TS35 DIN carrier rail EN 60715 Weight approx approx 0 25 kg approx 9 oz Protection class II Degree of protection IP 20 Mechanical degree of protection IK06 according to IEC 62262 Ambient temperature during operation Individual mounting 20 C 60 C 4 F 140 F Row mounting 20 C 50 C 4 F 122 F...

Page 98: ...led in the network connected to a switch hub with a straight cable or be connected directly to the computer with a cross link cable 12 1 1 Change the IP address of your computer Procedure 1 Right click Start Settings Control Panel Network Connections 2 Right click Local Area Connection Properties Using the left mouse button double click Internet Protocol TCP IP or click once then click Properties ...

Page 99: ...ress OK to register the entries and open the Fieldgate Web Server 3 The Fieldgate entry page appears in the browser You are registered with administrator rights and can now set up the Fieldgate communication parameters 4 Now change the IP address of the Fieldgate as described in chap 5 2 After the information has been sent to the Fieldgate contact will be broken off 5 Change the computer IP addres...

Page 100: ...device 4 20 mA x BINARY x tag Tagname device type INTRN vtime Timestamp Timestamp tag string Device tag hlsts1 string Limit value status of PV hltime1 Timestamp Timestamp change of limit value status of PV v1 float Process variable PV u1 float Unit of process variable PV vstslvl integer Device status 0 OK 1 Warning 2 Error vsts string Response code field device status hex type string Type of devic...

Page 101: ...y process value during operation PV min float Min value reached by process value during operation PV hy float Hysteresis for re entering limits PV swl float Switching level for switch status display swsts integer Text used to indicate change in switching status 1 uncovered covered 2 covered uncovered 3 on off 4 off on 5 empty full 6 full empty 7 good bad 8 bad good _t string Device name Tag intern...

Page 102: ...e GSM 24 Fieldgate identification 57 Fieldgate location 56 57 75 Firmware update 93 G Get Configuration File 62 GPRS support 14 H Hardware Configuration 76 Hardware installation 19 Hardware lock 70 Hardware version 76 Hysteresis 67 I Info 63 Input 61 75 Installation 5 Inventory Control 12 L Limit values 67 Logging on 53 71 M Mail 59 Mail setup 50 Menu bar 54 Message Text 53 Messagesl 49 Miscellane...

Page 103: ... Tag setup 73 Technical data 95 Telephone network 13 Time server setup 47 Trouble shooting 90 U User 58 User interface 54 User Mode 55 56 71 User Name 58 75 User roles 53 User Setup 58 V Viewing Information 71 W Web browser 38 97 Web Server 53 Wiring 21 X XML data 74 XML export 83 ...

Page 104: ......

Page 105: ......

Page 106: ...Fieldgate FXA320 12 Appendix Endress Hauser 104 www endress com worldwide ...