Cerabar S 4 to 20mA HART
Troubleshooting
Hauser
43
732 (E732)
Error
C
Factory
setting:
Warning
C>LRV Temp. user limits
exceeded
– Temperature measured value has
undershot the value specified for the
Tmin ALARM WINDOW parameter.
– Check system/temperature
measured value.
– Change value for Tmin ALARM
WINDOW if necessary. (
See also
Page 35, parameter description for
Tmin PROCESS.)
48
– Loose connection at sensor cable
– Wait a short period of time and
tighten the connection, or avoid
loose connection.
733 (E733)
Error
C
Factory
setting:
Warning
C>URV Temp. User limits
exceeded
– Temperature measured value has
overshot the value specified for the
Tmax ALARM WINDOW
parameter.
– Check system/temperature
measured value.
– Change value for Tmax ALARM
WINDOW if necessary. (
See also
Page 35, parameter description for
Tmax PROCESS.)
47
736 (A736)
Alarm
B
B>RAM error
– Fault in the main electronics.
– Briefly disconnect device from the
power supply.
4
– Main electronics defective.
– Replace main electronics.
737 (A737)
Alarm
B
B>Measurement error
– Fault in the main electronics.
– Briefly disconnect device from the
power supply.
20
– Main electronics defective.
– Replace main electronics.
738 (A738)
Alarm
B
B>Measurement error
– Fault in the main electronics.
– Briefly disconnect device from the
power supply.
19
– Main electronics defective.
– Replace main electronics.
739 (A739)
Alarm
B
B>Measurement error
– Fault in the main electronics.
– Briefly disconnect device from the
power supply.
23
– Main electronics defective.
– Replace main electronics.
741 (A741)
Alarm
B
B>TANK HEIGHT out of edit
limits
– LEVEL MIN or LEVEL MAX has
been changed.
– Perform reset (Code 2710) and carry
out calibration again.
44
742 (A742)
Alarm
B
B>Sensor connection error
(upload)
– Electromagnetic effects are greater
than specifications in the technical
data.
See Technical Information
TI00383P. This message normally
only appears briefly.
– Wait a few minutes.
– Perform reset (Code 7864) and carry
out calibration again.
18
– Cable connection sensor –main
electronics disconnected.
– Check cable connection and repair if
necessary.
– Sensor defective.
– Replace sensor.
743 (E743)
Alarm
B
B>Electronic PCB error during
initialization
– Electromagnetic effects are greater
than specifications in the technical
data.
See Technical Information
TI00383P. This message normally
only appears briefly.
– Wait a few minutes.
– Restart the device. Perform reset
(Code 62).
14
– Main electronics defective.
– Replace main electronics.
744 (A744)
Alarm
B
B>Main electronic PCB error
– Electromagnetic effects are greater
than specifications in the technical
data.
See Technical Information
TI00383P.
– Restart the device. Perform reset
(Code 62).
– Block off electromagnetic effects or
eliminate source of disturbance.
11
– Main electronics defective.
– Replace main electronics.
745 (W745)
Warning
C
C>Sensor data unknown
– Sensor does not suit the device
(electronic sensor nameplate).
Device continues measuring.
– Replace sensor with a suitable
sensor.
56
Code
Error type/
NA 64
Message/description
Cause
Measure
Priority