Cerabar S 4 to 20mA HART
Troubleshooting
Hauser
39
116 (W116)
Warning
C
C>Download error, repeat
download
– The file is defective.
– Use another file.
36
– During the download, the data are
not correctly transmitted to the
processor, e.g. because of open cable
connections, spikes (ripple) on the
supply voltage or electromagnetic
effects.
– Check cable connection PC –
transmitter.
– Block off electromagnetic effects or
eliminate sources of disturbance.
– Perform reset (Code 7864) and carry
out calibration again.
– Repeat download.
120 (E120)
Error
B
Factory
setting:
Warning
B>Sensor low pressure
– Pressure too low.
– Increase pressure until message
disappears.
30
– Sensor defective.
– Replace sensor.
121 (A121)
Alarm
B
B>Checksum error in factory
segment of EEPROM
– Main electronics defective.
– Replace main electronics.
5
122 (A122)
Alarm
B
B>Sensor not connected
– Cable connection sensor –main
electronics disconnected.
– Check cable connection and repair if
necessary.
13
– Electromagnetic effects are greater
than specifications in the technical
data.
See Technical Information
TI00383P.
– Block off electromagnetic effects or
eliminate source of disturbance.
– Main electronics defective.
– Replace main electronics.
– Sensor defective.
– Replace sensor.
130 (A130)
Alarm
B
B>EEPROM is defective.
– Main electronics defective.
– Replace main electronics.
10
131 (A131)
Alarm
B
B>Checksum error in EEPROM:
min/max segment
– Main electronics defective.
– Replace main electronics.
9
132 (A132)
Alarm
B
B>Checksum error in totalizer
EEPROM
– Main electronics defective.
– Replace main electronics.
7
133 (A133)
Alarm
B
B>Checksum error in History
EEPROM
– An error occurred when writing.
– Perform reset (Code 7864) and carry
out calibration again.
8
– Main electronics defective.
– Replace main electronics.
602 (W602)
Warning
C
C>Linearization curve not
monotone
– The linearization table is not
monotonic increasing or decreasing.
– Add to or correct linearization table.
Then accept linearization table
again.
57
604 (W604)
Warning
C
C>Linearization table not valid.
Less than 2 points or points too
close
– The linearization table consists of
less than 2 points.
– Add to linearization table. If
necessary, confirm linearization
table again.
58
– At least 2 points in the linearization
table are too close together. A
minimum gap of 0.5 % of the span
must be maintained between two
points.
Spans for the "Pressure linearized"
option: HYDR. PRESS MAX. –
HYDR. PRESS MIN.; TANK
CONTENT MAX. – TANK
CONTENT MIN.
Spans for the "Height linearized"
option: LEVEL MAX – LEVEL MIN;
TANK CONTENT MAX. – TANK
CONTENT MIN.
– Correct linearization table and
accept again.
613 (W613)
Warning
I
I>Simulation is active
– Simulation is switched on, i.e. the
device is not measuring at present.
– Switch off simulation.
60
Code
Error type/
NA 64
Message/description
Cause
Measure
Priority