Description of parameters
Cerabar S 4 to 20mA HART
16
Hauser
GET LRV (309)
Entry
Set lower range value – reference pressure is present at device.
The pressure for the lower current value (4 mA) is present at device. With the "Confirm"
option,
you assign the lower current value to the pressure value present.
Onsite display: the pressure value present is displayed in the bottom line.
Options:
• Abort
• Confirm
GET URV (310)
Entry
Set upper range value – reference pressure is present at device.
The pressure for the upper current value (20 mA) is present at device. With the "Confirm"
option, you assign the upper current value to the pressure value present.
Onsite display: the pressure value present is displayed in the bottom line.
Options:
• Abort
• Confirm
DAMPING VALUE (247)
Entry
Enter damping time (time constant
).
The damping affects the speed at which all subsequent elements, such as the onsite
display, measured value and current output react to a change in the pressure.
Input range:
0.0 to 999.0 s
Factory setting:
2.0 s or as per order specifications
Table 4: (GROUP SELECTION
) OPERATING MENU
SETTINGS
BASIC SETUP "Pressure"
Parameter name
Description