– Page 26 –
14
The unit is
ON
but the
Power Factor has not
improved.
Also, in this condition, if
there is;
• Under compensation
Alarm is ON
• All bank are ON
indication glow
Any Individual Step MCB/MCCB may
be tripped
Potential Malfunction of Dynamic
Switching Module (EDS).
Capacitor capacity reduction/ failure
d)
In case the Ready LED indication
is glowing but the remaining
indications are not glowing:
• Check for trigger voltage
(12v-20V).
• If this is not detected, check
the thermostat on the Heat
sink / Harmonic Reactor ther-
mostat as when these are open
(safety against high tempera-
ture opens these thermostats).
• Check the controller back side
T1, T2 terminals which is used
for over temperature trip it
has connected through panel
thermostat if it deducted the
over temperature then feed-
back goes to iSaver controller
then automatically all capacitor
banks will getting OFF one by
one.
• Then temperature comes
down the set point then isaver
function will work normally
normally panel internal temp
set was 55°C.
• If the thermostats are
found defective, replace
thermostat(s).
In case the Ready and Trigger LED
indication are glowing but yet the EDS
module indicates a trip indication there
is a Potential Thyristor malfunction/
failure and needs off-line repair.
15
Any Particular bank
taking less than rated
current/ KVAr.(less than
80%) at rated voltage
Capacitor may have been de-rated in
value
Replace the capacitor
16
Any particular bank
consuming current /
KVAr without controller
command
Thyristor may be faulty (short)
Check and replace the thyristor.