– Page 19 –
Mains CT primary
NOTE 1
NOTE 1
ISaver CT primary
600
1000
Clock
NOTE 2
NOTE 2
Calendar
NOTE 3
NOTE 3
Device ID
NOTE 4
NOTE 4
LCD power saver
DISABLED
DISABLED
Energy reset sure
NOTE 5
NOTE 5
NOTE 1: External mains CT primary value to be set.
NOTE 2: Local Time to be set
NOTE 3: Local Date to be set
NOTE 4: Corresponding communication ID to be set .if used, otherwise on setting required.
NOTE 5: To reset the energy and avg.PF when ever require. (It recommended during installation).
Default Control setup
Setting parameters
iSaver 450
iSaver 650
EB PF Set point
1.00
1.00
DG PF Set point
0.80
0.80
Connection delay
02.0
02.0
Reconnection delay
005
005
NO. of Banks
5
7
1
st
bank value
50
50
Operating sequence
1:2:2:2:2
1:2:2:2:2
Default Alarm setup
Setting parameters
iSaver 450
iSaver 650
Over voltage set(%)
110
110
Over current set (%)
120
120
Current THD (%)
30
30
Fan Temp Setup
Thermostat
Location
iSaver 450
Temp Range
in degree
Celsius
iSaver 650
Temp Range
in degree
Celsius
Front Door Fan
30
30
Back Door Fan
30
30
Front Temp Trip
50-55
50-55
Back Temp Trip
50-55
50-55