background image

Modbus communication protocol 

75 

Appendix A    Modbus Communication Protocol

 

A.1  Summary 

We provide general RS485 communication interface in our inverters for the user. Through 

this communication interface upper device (such as HMI, PC, PLC controller and etc.) can 
perform centralized monitor to the inverter (such as to set inverter parameter, control run of 
inverter, read work state of the inverter). 
    This communication protocol is interface criterion file designed for realizing 
above-mentioned function, please read it earnestly and program according to it so that realize 
long-distance and network control to the inverter.

 

 

A.2  Communication networking mode 

 

 
 
 
 
 
 
 
 

Fig.A-1 Networking graph

 

 

A.3  Communication mode 

At present,EN600PV inverter can be used only as Slave device in RS485 net. Can realize 

communication between inverters through PC, PLC or HMI if it needed. Specific communication 
mode is as mentioned below: 

(1) PC or PLC as mainframe

 inverter as Slave device, point-to-point communication 

between mainframe and Slave device. 

(2) Slave device don’t response when mainframe send out command by broadcast address. 
(3) User can set local address, baud rate and data format of the inverter through Slave device 

keypad or serial communication mode. 

(4) EN600PV provides the RS485 interface. 
(5) Default mode: Asynchronous serial

 semiduplex transport mode. There are RTU and 

ASCII two mode . Default format and transport rate: 8-N-1, 9600bps. 

 

A.4  Transmission mode 

Asynchronous serial, semiduplex transport mode. Default format and transport rate: 8-N-1, 

9600bps. The detail setting parameter, please refer to the F05 group function mode.(Remark: the 
parameter is valid under the Modbus communication, the other parameter comply with the original 
service manual) 

mainframe is PC 

mainframe is PLC 

232-485

conversion 

module 

EN600PV 

EN600PV

EN600PV 

EN600PV 

or 

RS232 

RS485

 

ENC

Summary of Contents for EN600PV Series

Page 1: ...PV Pump Inverter User Manual EN600PV Series Ver 1 0 ISO9001 2015 Quality Management System Authentication SHENZHEN ENCOM ELECTRIC TECHNOLOGIES CO LTD ...

Page 2: ... DP bus and other communication functions At the same time EN600PV series built in output default phase protection short circuit to the ground protection and other hardware protection functions effectively improve the reliability and safety of the system This brochure provides the installation and wiring settings fault check and methods maintenance and other relative issues to customer To ensure t...

Page 3: ...ption 14 4 2 3 LED and indicator light 15 4 2 4 Key board display status 15 4 2 5 User Management Parameters 17 4 2 6 Method for operating keypad 17 5 Function parameter schedule graph 20 5 1 Symbol description 20 5 2 Function parameter schedule graph 20 6 Debugging specification 60 6 1 Detailed function description of Solar inverter 60 6 1 1 System Parameter Group F00 60 6 1 2 On off input functi...

Page 4: ...cause inverter completely damage 2 Not allow for short circuit between and Otherwise it could cause inverter damage and power source short circuit 3 Forbid to install inverter on flammable objects otherwise it may cause fire 4 Do not install inverter in a environment with explosive gas it may cause explosion 5 Bare connection terminal should be insulation treatment after main loop connection other...

Page 5: ...V signal otherwise it may cause inverter completely damage 2 Do not install and run inverter when inverter damage or spare part less otherwise it may cause fire or human injury 3 Inverter should install in a place where can accept itself weight otherwise it may cause inverter drop down or belongings damage E N C ...

Page 6: ... contact our company or local agent rapidly if some careless omission or mistake arise we ll deal with it as soon as possible 2 2 Type explanation EN600PV 4T 0015 Fig 2 1 Type description 2 3 Nameplate explanation Nameplate presented as Fig 2 2 with type and rating data at the bottom of inverter right side Fig 2 2 Nameplate Code Name EN600PV Series No Code Volt grade 2S 1 phase220V 4T 3 phase 380V...

Page 7: ...00PV 4T0022 5 2 2 2 86 780 600 750 EN600PV 4T0037 8 5 3 7 4 8 780 600 750 EN600PV 4T0055 13 5 5 7 2 780 600 750 EN600PV 4T0075 17 7 5 9 75 780 600 750 EN600PV 4T0110 25 11 14 3 780 600 750 EN600PV 4T0150 33 15 19 5 780 600 750 EN600PV 4T0185 39 18 5 24 780 600 750 EN600PV 4T0220 45 22 28 6 780 600 750 EN600PV 4T0300 60 30 39 780 600 750 EN600PV 4T0370 75 37 48 780 600 750 2 5 EN600 Appearance and ...

Page 8: ... 186 5 Fig a EN600PV 2S0007 EN600PV 2S0015 EN600PV 2S0022 EN600PV 2S0037 EN600PV 4T0007 EN600PV 4T0015 EN600PV 4T0022 EN600PV 4T0037 EN600PV 4T0055 140 240 175 188 129 227 5 Fig a EN600PV 4T0075 EN600PV 4T0110 180 304 189 202 165 281 6 Fig a EN600PV 4T0150 EN600PV 4T0185 250 398 210 223 180 382 9 Fig b EN600PV 4T0220 EN600PV 4T0300 280 450 240 253 180 434 9 Fig b EN600PV 4T0370 H W A B D D2 安装孔 B ...

Page 9: ...ans Running frequency specified channel Main auxiliary specified to a realize one main adjusting and one fine control Digital specified analog specified pulse specified pulse width specified communication specified and others which can be switched by many means at any time Binding function Run command channel and frequency specified channel can bind together randomly and switch synchronously Input...

Page 10: ...rotection over current protection over voltage protection under voltage protection over heat protection overload protection under load protection relay absorption protection terminal protection and no stop protection under power off Environment Application site Indoor not bare to sunlight no dust no corrosive gas no flammable gas no vapor no water drop or salt etc Altitude Under 1000 meter above 1...

Page 11: ...ect power source DC volt Positive terminal PB External connect to brake resistor reverse terminal DC volt Negative terminal U V W 3 phase AC output terminal connect to motor Grounding terminal EN600PV 4T0007 EN600PV 4T0150 R S T 3 phase AC input terminal connect power source DC volt Positive terminal PB External connect to brake resistor reverse terminal DC volt Negative terminal U V W 3 phase AC ...

Page 12: ...reactor External connect to brake resistor reverse terminal DC volt Positive terminal DC volt Negative terminal U V W 3 phase AC output terminal connect to motor Grounding terminal R S T U PB V W The wiring of main loop must connect right according to the description above Wrong wiring will cause device damage and personal injury E N C ...

Page 13: ... SW3 GND TC TB TC close TA TC open TB 485 485 485 communication port Twisted pair cable Analog input type SW1 switch AI1 valid Brake unit external connect fitting part U V W Y3 Y4 DO Multi function R S T Ampere meter 4 20mA Voltmeter 0 10V V 0 10V A 4 20mA Open Close Com mon TA Relay load X7 7 8 PW 24V X terminal active electric level support high level and low level COM Y1 Y2 24V A01 AO2 switch S...

Page 14: ...1 4000 AI2 Analog output 2 Input range DC 10V 10V 4 20mA selected by the second figure of F00 20 and SW2 dial switch on control board Input impedance voltage input at 20KΩ Current input at 250Ω Resolution 1 2000 Analog output AO1 Analog output 1 Voltage or current output is selected by SW3 AO1 and SW4 AO2 dial switch on control board Output voltage range 0 10V Output current range 4 20mA AO2 Analo...

Page 15: ...liary interface CN2 retain CN6 StandardRS485 communication interface Twisted pair cable or shield wire to connect 2 RS485 crystal outlet CN6 layout as following 12345678 RS485 terminal CN6 layout No 1 2 3 4 5 6 7 8 Name 485 485 E N C ...

Page 16: ...ive parameter F12 00 0 and the PV terminal prohibition function of input terminal No 72 is invalid the inverter will enter the PV operation mode 2 Common run Common open loop run mode of general inverter In above 6 kinds of run mode except jog run the inverter can run according to kinds of frequency setting method 4 2 Operation and use of key board 4 2 1 Keypad layout The operating keyboard is the...

Page 17: ...l be stopped according to set mode after pressing this key if run command channel is set as keypad stop effective mode The inverter will be reset and resume normal stop status after pressing this key when the inverter is in malfunction status Digital potentiometer It is the same as the function of increase and decrease key rotate to the left means decrease rotate to the right means increase Increa...

Page 18: ... that the inverter output reverse phase order and the connected motor rotate in reverse direction 4 2 4 Key board display status EN600PV keypad display status is classified as Waiting status parameter display Function code parameter editing status display Malfunction alarm status display Run status parameter display Alarm state display in total 5 kinds of status LED indicator light will all be lit...

Page 19: ...to editing status If user password is set can enter into editing status after inputting the password see also F27 00 description and editing status is displayed according to three classes menu mode as shown in Fig 4 5 To press key can enter into one class by one class Under function parameter display status to press key to carry on parameter storage operation To press key can only come back to upp...

Page 20: ...ate Advanced menu mode and user menu mode Basic menu F00 F01 F02 F03 F26 Middle menu F00 F01 F02 F03 F04 F05 F06 F07 F08 F09 F10 F11 F12 F13 F14 F15 F16 F18 F19 F26 Advance menu F00 F01 F02 F03 F04 F05 F06 F07 F08 F09 F10 F11 F12 F13 F14 F15 F16 F17 F18 F19 F20 F21 F22 F23 F24 F25 F26 F27 User custom F00 00 and F25 parameters group 4 2 6 Method for operating keypad Can carry on various operation t...

Page 21: ...eter 3 See about failure parameter under failure status If press key under failure status the user can quickly locate to the F26 group function code parameter Press can quickly switch value between F26 04 F26 10 parameters and fault alarm easy to view the fault records 4 Keypad key press locking operation Under monitoring situation To press for 5s the keyboard will display LOCH1 now the buttons on...

Page 22: ...Run and operation explanation for inverter 19 of hundred unit of F00 14 5 Keypad key press unlocking operation Under keypad locked situation press key for more than 5s to unlock the keypad E N C ...

Page 23: ...ency 0 01Hz 3 Output frequency 0 01Hz 4 Output current 0 1A 11kW show 0 01A 5 Output voltage 1V 6 DC busbar voltage 0 1V 7 Motor speed 1 circle min 8 Motor line velocity 1 circle min 9 Inverter temperature 1 10 Run time already this time 0 1min 11 Current accumulate run time 1h 12 Current accumulate power on time 1h 13 Inverter status 14 Input terminal status 15 Output terminal status 16 Extension...

Page 24: ...ion 54 Current output torque percentage relative to rated torque with direction 55 DC Bus current 0 1A 56 Flux current speed 0 3 m3 h 57 Open circuit voltage 0 1V 58 Output power active power 0 1KW 59 The low digit of Total power consumption 1 kwh 60 The high digit of Total power consumption 1 represents 10000 kwh 61 Daily power generation 0 1kwh 62 Daily traffic 0 1 m3 63 Cumulative flow low 1m3 ...

Page 25: ...arameters return to default not include F15 and F26 group parameter 3 Extension parameter return to default only F21 F24 group parameter return to default 4 Virtual parameter return to default only F20 group parameter return to default 5 Fault record return to default only fault record parameter group F26 group parameter return to default Hundreds digit Key operation 0 All locked 1 Except button t...

Page 26: ... 0 10V input 1 10 10V input 2 4 20mA input Thousands digit EAI2 configuration 0 0 10V input 1 10 10V input 2 4 20mA input 1 1100 F00 21 Analog output terminal configuration Units digit AO1 configuration 0 0 10V output 1 4 20mA output Tens digit AO2 configuration 0 0 10V output 1 4 20mA output Hundreds digit EAO1 configuration 0 0 10V output 1 4 20mA output Thousands digit EAO2 configuration 0 0 10...

Page 27: ...ontrol Only when parameter F01 00 0 3 4 valid Units digit power down reserve setup 0 Main frequency power down reserve 1 Main frequency power down no reserve Tens digit halt reserve setup 0 Halt main frequency hold 1 Halt main frequency recovery F01 01 Hundreds digit Set of communication presetting frequency dimension 0 Preset of absolute frequency mode preset 5000 represent 50 00Hz 1 Preset 10000...

Page 28: ... frequency Auxiliary frequency 2 F01 11 polarity opposed of main and auxiliary frequency complex frequency is zero 1 0 F01 07 Auxiliary frequency provide coefficient 0 00 10 00 0 01 1 00 F01 08 Coefficient after complex of main and auxiliary frequency 0 00 10 00 0 01 1 00 F01 09 Auxiliary frequency range selection 0 Relative upper limit frequency 1 Relative main frequency 1 0 F01 10 Auxiliary freq...

Page 29: ...r type F01 19 Acc Dece time unit 0 0 01s 1 0 1s 2 1s 1 1 F01 20 Acc Dece mode selection 0 Line acc Dece mode 1 S curve acc Dece mode 1 0 F01 21 S curve acceleration initiation segment time 10 0 50 0 Acceleration deceleration time S curve deceleration start time S curve deceleration raise time 90 0 1 20 0 F01 22 S curve Acceleration up segment time 10 0 70 0 Acceleration deceleration time S curve a...

Page 30: ...stop DC braking waiting time 0 00 30 00s 0 01s 0 00s F02 16 Stop DC braking current 0 0 100 0 0 1 0 0 F02 17 Stop DC braking time 0 0 30 0s 0 1s 0 0s F02 18 Stop auxiliary braking current 0 0 100 0 0 1 0 0 F02 19 Stop auxiliary braking time 0 0 100 0s 0 1s 0 0s F02 20 Forward reverse dead zone time 0 0 3600 0s 0 1s 0 0s F02 21 Forward reverse switching mode 0 Over zero frequency switchover 1 Over ...

Page 31: ...voltage 0 01 80 00 F03 12 V F oscillation suppression factor 0 255 1 10 F04 Auxiliary running parameter group Function code Name Set range Min unit Factory default Modifi cation F04 00 Jump freq 1 0 00Hz Upper limit frequency 0 01Hz 0 00Hz F04 01 Jump freq 1 range 0 00Hz Upper limit frequency 0 01Hz 0 00Hz F04 02 Jump freq 2 0 00Hz Upper limit frequency 0 01Hz 0 00Hz F04 03 Jump freq 2 range 0 00H...

Page 32: ...0 1 200 F04 28 Acceleration time 8 1 60000 1 200 F04 29 Deceleration time 8 1 60000 1 200 F04 30 Acceleration time 9 1 60000 1 200 F04 31 Deceleration time 9 1 60000 1 200 F04 32 Acceleration time 10 1 60000 1 200 F04 33 Deceleration time 10 1 60000 1 200 F04 34 Acceleration time 11 1 60000 1 200 F04 35 Deceleration time 11 1 60000 1 200 F04 36 Acceleration time 12 1 60000 1 200 F04 37 Deceleratio...

Page 33: ... Modbus agreement response selection 0 Respond mainframe demand and respond data package 1 Respond mainframe demand without response response when write parameter 2 Respond mainframe demand without response without response when write parameter Thousands digit Communication Sets power down reserve setup 0 No reserve 1 Reserve 1 0000 F05 03 Local address 0 247 Modbus protocol 0 is the broadcast add...

Page 34: ... function 0 90 1 0 F05 13 Communication virtual terminal CX4 function 0 90 1 0 F05 14 Communication virtual terminal CX5 function 0 90 1 0 F05 15 Communication virtual terminal CX6 function 0 90 1 0 F05 16 Communication virtual terminal CX7 function 0 90 1 0 F05 17 Communication virtual terminal CX8 function 0 90 1 0 F05 18 Input mapping application parameter 1 F00 00 F26 xx 0 01 25 00 F05 19 Inpu...

Page 35: ...e inverter 1 hour F06 Setting curve parameter group Function code Name Set range Min unit Factory default Modifi cation F06 00 Setting curve selection Units digit AI1 curve selection 0 Curve 1 1 Curve 2 2 Curve 3 Tens digit AI2 curve selection The same as Units digit Hundred digit rapid pulse curve selection The same as Units digit Thousands digit pulse width setting curve selection The same as Un...

Page 36: ...ng physical quantity 1 0 0 of the corresponding physical quantity Tens digit curve 2 setting Same as units digit Hundreds digit curve 3 setting Same as units digit Thousands digit extended curve 1 Same as units digit Ten thousands digit extended curve 2 Same as units digit 1 11111 F07 Analog Pulse input function parameter group Function code Name Set range Min unit Factory default Modifi cation F0...

Page 37: ...opened time 0 00 99 99s 0 01s 0 00s F08 06 X3 Input terminal closed time 0 00 99 99s 0 01s 0 00s F08 07 X3 Input terminal opened time 0 00 99 99s 0 01s 0 00s F08 08 X4 Input terminal closed time 0 00 99 99s 0 01s 0 00s F08 09 X4 Input terminal opened time 0 00 99 99s 0 01s 0 00s F08 10 X5 Input terminal closed time 0 00 99 99s 0 01s 0 00s F08 11 X5 Input terminal opened time 0 00 99 99s 0 01s 0 00...

Page 38: ...ter running prohibited Stop according to the stop mode 29 Acceleration deceleration prohibited command 30 Three wire running control 31 Process PID invalid 32 Process PID stop 33 Process PID integral holding 34 Process PID integral resetting 35 Process PID function negation Closed loop adjustment feature negation 36 Simple PLC invalid 37 Simple PLC halted 38 Simple PLC stop state resetting 39 Main...

Page 39: ...ction selection Same as above 1 2 F08 20 Input terminal X3 function selection Same as above 1 0 F08 21 Input terminal X4 function selection Same as above 1 0 F08 22 Input terminal X5 function selection Same as above 1 0 F08 23 Input terminal X6 function selection Same as above 1 0 F08 24 Input terminal X7 function selection Same as above 1 0 F08 25 Input terminal X8 function selection Same as abov...

Page 40: ...evel detect signal 2 FDT2 15 Output frequency arrival upper limit FHL 16 Output frequency arrival low limit FLL 17 Frequency 1 arrival output 18 Frequency 2 arrival output 19 Overload pre alarm signal OL 20 Undervoltage lockout stop LU 21 External fault stop EXT 22 Fault 23 Alarm 24 Simple PLC operation 25 Simple PLC section operation finish 26 Simple PLC circle operation finish 27 Simple PLC oper...

Page 41: ...FDT2 lag 0 00 50 00Hz 0 01Hz 1 00Hz F09 10 Zero frequency signal detection value 0 00Hz upper limit frequency 0 01Hz 0 40Hz F09 11 Zero frequency backlash 0 00Hz upper limit frequency 0 01Hz 0 10Hz F09 12 Zero current detection amplitude 0 0 50 0 0 1 0 0 F09 13 Zero current detection time 0 00 60 00s 0 01s 0 1s F09 14 Over current detection value 0 0 250 0 0 1 160 0 F09 15 Over current detection t...

Page 42: ...time 0 000 50 000s 0 001s 0 000s F09 35 Analog output AO1 selection 0 Output frequency before slip compensation 0 00Hz upper limit frequency 1 Output frequency after slip Compensation 0 00Hz upper limit frequency 2 Setup frequency 0 00Hz upperlimit frequency 3 Main setting frequency 0 00Hz upper limit frequency 4 Auxiliary setting frequency 0 00Hz upperlimit frequency 5 Output current 1 0 2 invert...

Page 43: ... 00s F10 Simple PLC Multi speed Function Parameter Group Function code Name Set range Min unit Factory default Modifi cation F10 00 Simple PLC operate setting Units digit Run mode selection 0 Inaction 1 Stop after single cycle 2 Final value keep after single cycle 3 Continuous cycle Tens digit Interrupt run restart mode selection 0 Restart from first phase 1 Continuous run from phase frequency at ...

Page 44: ...1 running time 0 6000 0 0 1 10 0 F10 17 Step 2 running time 0 6000 0 0 1 10 0 F10 18 Step 3 running time 0 6000 0 0 1 10 0 F10 19 Step 4 running time 0 6000 0 0 1 10 0 F10 20 Step 5 running time 0 6000 0 0 1 10 0 F10 21 Step 6 running time 0 6000 0 0 1 10 0 F10 22 Step 7 running time 0 6000 0 0 1 10 0 F10 23 Step 8 running time 0 6000 0 0 1 10 0 F10 24 Step 9 running time 0 6000 0 0 1 10 0 F10 25 ...

Page 45: ...Pulse provision 6 Communication provision Communication address 1D00 7 Reserved 1 0 F11 02 Feedback channel selection 0 AI1 analog input 1 AI2 analog input 2 EAI1 analog input Extend effective 3 EAI2 analog input Extend effective 4 AI1 AI2 5 AI1 AI2 6 Min AI1 AI2 7 Max AI1 AI2 8 Pulse input 9 Communication feedback address is 1DOC 4000 stands for 10 00V 1 0 F11 03 Provision channel filtering time ...

Page 46: ...4 Multiple closed loop provision 2 0 00 10 00V 0 01V 0 00V F11 25 Multiple closed loop provision 3 0 00 10 00V 0 01V 0 00V F11 26 Multiple closed loop provision 4 0 00 10 00V 0 01V 0 00V F11 27 Multiple closed loop provision 5 0 00 10 00V 0 01V 0 00V F11 28 Multiple closed loop provision 6 0 00 10 00V 0 01V 0 00V F11 29 Multiple closed loop provision 7 0 00 10 00V 0 01V 0 00V F12 Solar Functional ...

Page 47: ...2 23 Overcurrent protection automatic recovery time 0 0s 6000 0s 0 1s 10 0s F12 24 Alarm recovery mode Unit Low Frequency Protection A 42 0 Automatic recovery 1 Manual recovery Ten places Dry pumping protection A 43 0 Automatic recovery 1 Manual recovery Set sequence switching Hundreds Overcurrent protection A 44 0 Automatic recovery 1 Manual recovery Thousands Minimum Power Protection A 45 0 Auto...

Page 48: ...ter manually Tens digit 0 Variable swing 1 Fixed swing Hundreds digit Traverse halt start mode selection 0 Restart 1 Start as previous halt record Thousands digit Traverse status reserve selection 0 No reserve 1 Reserve 1 0000 F13 02 Traverse frequency swing value 0 0 50 0 0 1 10 0 F13 03 Sudden Jump frequency 0 0 50 0 0 1 2 0 F13 04 Traverse cycle 0 1 999 9s 0 1s 10 0s F13 05 Triangular wave risi...

Page 49: ...op low speed proportional gain 0 1 80 0 This parameter is valid when F00 24 1 or 2 0 1 20 0 F14 04 Speed loop low speed integral time 0 001 10 000s This parameter is valid when F00 24 1 or 2 0 001s 0 020s F14 05 Speed loop parameter switching frequency 0 00Hz 20 00Hz This parameter is valid when F00 24 1 or 2 0 01Hz 5 00Hz F14 06 Low frequency power generation stability coefficient 0 50 This param...

Page 50: ...l setting Determined by F14 10 1 AI1 analog setting 2 AI2 analog setting 3 Terminal UP DOWN adjustment setting 4 Reserved 5 EAI1 analog Setting Extended Valid 6 EAI2 analog setting Extended Valid 7 High speed pulse setting X8 terminals need to select the appropriate function 8 Terminal pulse width setting X8 terminals need to select the appropriate function Note The maximum value of 1 8 channels c...

Page 51: ...t value in Torque control mode 0 00Hz upper limit frequency This parameter is valid when F00 24 1 0 01Hz 50 00Hz F14 19 Reverse speed limit value in Torque control mode 0 00Hz upper limit frequency This parameter is valid when F00 24 1 0 01Hz 50 00Hz F14 20 Torque Accelerate Decelerate time setting 0 000 60 000s This parameter is valid when F00 24 1 0 001s 0 100s F14 21 Torque compensation 0 0 100...

Page 52: ...election 0 Inaction 1 Asynchronous motor stop to self adjusting 2 Asynchronous motor rotate no load to self adjusting 3 Reserved Note Before adjustment The nameplate data should be setting directly Motor parameter group can have special default values or can be modified by users or can be self adjusted when parameter F15 01 is modified the other parameters of the motor will turn into default value...

Page 53: ...single step s size setup 0 01 10 00Hz 0 01Hz 0 10Hz F18 08 Droop control decline frequency 0 00 10 00Hz 0 01Hz 0 00Hz F18 09 Setup accumulate power on time 0 65535 hours 1 0 F18 10 Setup accumulate run time 0 65535 hours 1 0 F18 11 Timing run function enable 0 Invalid 1 Valid 1 0 F18 12 Timing run stop time 0 1 6500 0Min 0 1Min 2 0Min F18 13 Currently run arrival time 0 0 6500 0Min 0 1Min 1 0Min F...

Page 54: ... reference channel 0 Digital setting Determined by 18 23 1 AI1 analog setting 2 AI2 analog setting 3 Terminal UP DOWN adjustment setting 4 Reserved 5 EAI1 analog Setting Extended Valid 6 EAI2 analog setting Extended Valid 7 High speed pulse setting X8 terminals need to select the appropriate function 8 Terminal pulse width setting X8 terminals need to select the appropriate function Note The maxim...

Page 55: ...ault free halt 1 00 F19 11 Input output phase loss short circuit detection action Units digit Input phase loss 0 No detection 1 Fault free halt Tens digit Output phase loss 0 No detection 1 Fault free halt Hundreds digit Power on on earth short circuit protect detection enable 0 No detection 1 Fault free halt Thousands digit Operation on earth short circuit protect detection enable 0 No detection ...

Page 56: ...F19 28 Feedback lost detection time 0 0 500 0s 0 1s 0 5s F19 29 Deviation magnitude abnormal detection value 0 100 1 50 F19 30 Deviation magnitude abnormal detection time 0 0 500 0s 0 1s 0 5s F19 31 Protection action selection 1 Units digit PID provide loss detection act 0 No detection 1 Alarm Continue run 2 Alarm Stop run as halt mode 3 Fault Free halt Tens digit PID feedback loss detection act 0...

Page 57: ...l for standby 1 0 F19 37 Abnormal standby frequency 0 00Hz upper limit frequency 0 01Hz 10 00Hz F19 39 Over speed OS detection time 0 0 120 0 equals upper limit frequency 0 1 120 0 F19 40 Over speed OS detection time 0 00 20 00s No detection when value is 0 0 01s 0 00s F19 41 Detection value when speed deviation DEV is too large 0 0 50 0 equals upper limit frequency 0 1 10 0 F19 42 Detection time ...

Page 58: ... time 0 00 600 00s 0 01s 0 00s F20 15 Virtual output VDO1 close delay time 0 00 600 00s 0 01s 0 00s F20 16 Virtual output VDO2 close delay time 0 00 600 00s 0 01s 0 00s F20 17 Virtual output VDO3 close delay time 0 00 600 00s 0 01s 0 00s F20 18 Virtual output VDO4 close delay time 0 00 600 00s 0 01s 0 00s F20 19 Virtual output VDO5 close delay time 0 00 600 00s 0 01s 0 00s F20 20 Virtual input VDI...

Page 59: ...0s 0 1s 0 0s F24 04 EAO2 Gain 0 2 00 0 01 1 00 F24 05 EAO2 Bias 0 100 0 0 10 0 00 F24 06 EAO1 Filter time 0 20 0s 0 1s 0 0s F24 07 EAO1 Bain 0 2 00 0 01 1 00 F24 08 EAO1 Bias 0 100 0 0 10 0 00 F24 09 F24 13 Reserved F25 User Definition Display Parameter Group Function code Name Set range Min unit Factory default Modifi cation F25 00 User Function Code 1 F00 00 F25 xx 0 01 25 00 F25 01 User Functio...

Page 60: ...5 29 User Function Code 30 F00 00 F25 xx 0 01 25 00 F26 Fault Record Function Parameter Group Function code Name Set range Min unit Factory default Modifi cation F26 00 The last fault record 0 No fault 1 Overcurrent at acceleration 2 Overcurrent at deceleration 3 Overcurrent at constant speed 4 Overvoltage at acceleration 5 Overvoltage at deceleration 6 Overvoltage at constant speed 7 Overvoltage ...

Page 61: ...5V 0 1V 0 0V F26 08 Module temperature at the last one fault 0 125 1 0 F26 09 Input terminal status at the last one fault 0 F26 10 Accumulated run time at the last one fault 0 65535min 1min 0min F26 11 Setup frequency at the last two fault 0 00Hz upper limit frequency 0 01Hz 0 00Hz F26 12 Output frequency at the last two fault 0 00Hz upper limit frequency 0 01Hz 0 00Hz F26 13 Output current at the...

Page 62: ...on C 00 Display the parameter of F00 01 F00 07 definition C 01 Display the parameter of F00 02 F00 08 definition C 02 Display the parameter of F00 03 F00 09 definition C 03 Display the parameter of F00 04 F00 10 definition C 04 Display the parameter of F00 05 F00 11 definition C 05 Display the parameter of F00 06 F00 12 definition E N C ...

Page 63: ...ing and then return to C 00 parameter monitor For example pressing parameter switch from C 00 to C 01 continuous pressing the same button parameter switch from C 01 to C 02 then pressing return to C 00 parameter monitor 55 DC busbar current 0 1A 56 Flow speed 0 1 m3 h 57 Open circuit voltage 0 1 V 58 Output Power active power 0 1Kw 59 Cumulative power low position 1Kwh 60 Cumulative power high pos...

Page 64: ...ions please see table 6 1 Table 6 1 Multi functional input selection function table Content Function Content Related Function 70 Full water inspection alarm A 46 72 function prohibition on solar inverter 71 Reset of full water alarm 70 Full water alarm A 46 During the operation of the frequency converter this function is effective and after maintaining F12 28 time it enters the standby state of fu...

Page 65: ...el F12 04 Voltage increase threshold Range 0 5 30 0 0 5 This parameter defines the varying voltage within the search interval in Mppt mode F12 05 Proportional gain Kp Range 0 00 100 00 Determine by VFD type F12 06 Integral gain Ki Range 0 01 10 00 Determine by VFD type F12 07 Differential gain Kd Range 0 00 10 00 Determine by VFD type F12 05 F12 07 define PID coefficients in photovoltaic mode The ...

Page 66: ...ntaining F12 14 times it will exit the low frequency protection state and start running again F12 15 0 or F12 16 0 this function is invalid F12 18 Minimum power protection value Range 0 00 100 00Kw 0 00Kw F12 19 Minimum power protection time Range 0 0 6000 0s 10 0s F12 20 Minimum power recovery time Range 0 0 6000 0s 10 0s Minimum power protection function Under the photovoltaic mode when the inve...

Page 67: ... the overcurrent protection state and starts running again F12 25 0 or F12 26 0 this function is invalid F12 28 Full Water protection detection time Range 0 0 6000 0s 10 0s F12 29 full water protection exit time Range 0 0 6000 0s 10 0s When the photovoltaic inverter is in operation function terminal No 70 is effective and after maintaining F12 28 times it enters the full water standby state and th...

Page 68: ...he solar panel terminals to the inverter R T or bus Please note that the and connected to the frequency converter cannot be reversed otherwise it will blow up the plane Connect the inverter s U V W to the motor and ground of inverters connection motor ground wire 2 Parameter setting and trial run Set F00 24 0 V F mode operation F01 15 0 keyboard operation reasonable set F01 11 upper limit frequenc...

Page 69: ...ent of the inverter is bigger than F12 21 and maintained for F12 22 time the inverter will enter the overcurrent protection state The operating frequency will be reduced to 0 00Hz and A 44 warning will be displayed The system is in the overcurrent protection state and after maintaining F12 23 it will exit the overcurrent protection state and start running again F12 21 0 or F12 22 0 this function i...

Page 70: ...put power supply Too small power of the inverter Choose inverter with high power Output phase lose under vector control Check whether the motor wiring is in good condition E 02 Overcurrent during decelerating process Decelerating time is too short Prolong decelerating time Have potential energy load or big Inertia load Have potential energy load or big Inertia load Power of inverter is a bit small...

Page 71: ...rotection The operating current of inverter less than underload threshold Confirm whether the parameters F19 08 F19 09 setting are reasonable load divorced from motor Checking whether the load divorced from motor E 12 The input phase lose The three phase input power supply is abnormal Check the three phase input power line is off or poor contact Power supply board anomaly Look for service from man...

Page 72: ...the fan E 18 A 18 External device failure External fault emergency stop terminal closed Disconnect external fault terminals after handling external faults E 19 Current detecting circuit failure The connection or the plug in of the control board is loose Check and connect the wire again Assistant power supply damaged Look for service from manufacturer or agent Hall component damaged Look for servic...

Page 73: ...tection circuit is abnormal Look for service from manufacturer or agent E 32 Self tuning failure Motor parameters are not set according to the nameplate set parameter correctly according to the motor nameplate Abnormal current during tuning Select inverter match the motor Motor wiring is incorrect Check the motor three phase wiring E 33 A 33 Contactor is abnormal The power board is abnormal Look f...

Page 74: ...ameter setting error F01 00 and F01 03 cannot be set to the same channel 9 terminal encoder given except A 52 Terminal function exclusiveness alarm Terminal function parameters setting repeatedly Check the terminal function settings A 53 Operation limit alarm Limit run time Please contact the superior supplier LOCH1 Keypad lock Keypad lock Press key for more than 2s to unlock the keypad 7 2 Failur...

Page 75: ...r to annex description 4 Cut off power supply 7 4 Alarm reset When an alarm occurs must eliminate alarm source which cause alarm otherwise the alarm cannot be eliminated also cannot be reset by reset button 1 Before reset you must find out reason of failure downright and eliminate it otherwise may cause permanent damage to the inverter 2 If can t reset or failure takes place again after resetting ...

Page 76: ...ck whether wiring terminals have arc trace The main circuit insulation test Recommend to inspect with following instrument Input voltage electric voltmeter output voltage rectifying voltmeter input output current pincers ammeter 8 2 Inspection and replacement of damageable parts Some component parts in the inverter will be abraded or bear descending performance for long term usage To assure that t...

Page 77: ...st which is subject to contract if any 4 You can contact the agent and also our company directly if you have questions After repair guarantee period we shall also provide lifetime charged repair service for our products 8 4 Storage The user must pay attention to following points for temporary storage and long term storage after purchasing the inverter 1 Avoid storing the inverter in high temperatu...

Page 78: ...s through PC PLC or HMI if it needed Specific communication mode is as mentioned below 1 PC or PLC as mainframe inverter as Slave device point to point communication between mainframe and Slave device 2 Slave device don t response when mainframe send out command by broadcast address 3 User can set local address baud rate and data format of the inverter through Slave device keypad or serial communi...

Page 79: ...es are sent at least 3 5 character time interval pause The first transmitted field is device address the character you can transfer is hexadecimal 0x00 0xFF Network equipment Continuously monitor the bus including pauses When the address field is received all equipment determine whether it is sent to their own when the last character of the packet transfer is complete at least a 3 5 character time...

Page 80: ... code LRC CHK Lo Closing Flag Hi Closing Flag Hi CR 0x0D Closing Flag Lo Closing Flag Lo LF 0x0A A 5 2 Host read slave parameter Command code 03H Host can read one or more parameter up to ten by initiating a communication transaction E g read 2 contiguous inverter parameter values from the address 0000H of inverter whose address is 01 the contents of host command ADR 01H CMD 03H Parameters initial...

Page 81: ...up communication address Inverter function parameter s MODBUS communication address addressing process follows PPnn way PP means high byte of the address corresponding to function parameter s group number nn means low byte of the address corresponding to function code parameter s group internal code For example F3 21 function code s communication address is 0315H 03H is the hex form of group numbe...

Page 82: ... 2 C 02 1C02H reading only Monitoring parameters 3 C 03 1C03H reading only Monitoring parameters 4 C 04 1C04H reading only Monitoring parameters 5 C 05 1C05H reading only Monitoring parameters 6 A 6 4 Inside hidden parameters Variable name Communication address Read write attribute Means of command data or response value PID Communication presetting value 1D00H Read write Range 0 1000 1000 represe...

Page 83: ...60000 represents 600 00Hz PID feedback voltage 1D0CH Read write Range 0 4000 4000 represents 10 00V Reserved 1D0DH A 7 Communication error processing Inverter receiving data packet detection error it finds reading writing parameter address or parameter value invalid so reply to the host with communication error response packet Communication error response packet host command code 80H as command co...

Page 84: ...w byte Data High byte Data Low byte CRC low bit CRC high bit host command frames 01 06 1E 00 00 06 0F E0 Slave respond frames 01 06 1E 00 00 06 0F E0 3 Set 1 inverter given value to 50 00Hz Data Field Slave Address Order code Register address High byte Register address Low byte Data High byte Data Low byte CRC low bit CRC high bit host command frames 01 06 1E 01 13 88 D3 74 Slave respond frames 01...

Page 85: ...d do not send Modbus protocol without host address Command code Reading the command of parameter or data from inverter the value is 0 3 Register address The internal memory address of inverter function parameter is of 4 byte which is ASCII mode transformed from Hexadecimal Corresponding relation between specific parameters and memory address can be seen in the later table Register number The numbe...

Page 86: ...ecimal Range 4 40 byte Checksum From slave address to the character before checksum the LRC checksum of the character string The function terminal can be seen in the later text Ending symbol enter line break Is 0x0D 0x0A The followings are the example of command frame and return frame all the Data are ASCII character Inquiry frame 0 1 0 3 0 0 0 1 0 0 0 1 FA n r The detail introduction of every byt...

Page 87: ...ation between parameter and storage address can be seen in the later excel Data The new value of revised parameter Checksum From slave address to the character before checksum the LRC checksum of the character string Response frame Response frame format Frame begin symbol Slave address Slave address Command code Command code Register address Register address Register address Register address Data ...

Page 88: ...iting parameter 1 3 8 8 the value of writing parameter 5 C 0 1 0 6 0 1 0 1 1 3 8 8 for LRC checksum 0x5C 0x100 0x01 0x06 0x01 0x01 0x13 0x88 A 9 CRC checkout mode CRC checkout value calculating function written by C language is as follows unsigned int cal_crc_value unsigned char pval unsigned char len unsigned int crc_value 0xFFFF unsigned int i while len crc_value pval for i 0 i 8 i if crc_value ...

Page 89: ...Modbus communication protocol 86 crc_value 1 crc_value 0xA001 else crc_value 1 return crc_value E N C ...

Page 90: ...Optional 3 EN CAN1 CANopen expansion card Optional 4 EN CAN2 CANlink expansion card Optional B 2 Selection for isolated form of 485 communication extension card It is specially developed to provide 485 communication functions for inverters adopting isolated solution the electrical parameters meet international standards Users can choose according to their needs to control operation and parameter s...

Page 91: ...lectric Technologies CO LTD Address 5F Bldg 4 Minqi Technology Park Lishan Rd Nanshan Area Shenzhen 518055 China Website www encvfd com E mail encvfd encvfd com encvfd enc net cn Tel 86 755 26984485 Fax 86 755 26985120 ...

Reviews: