Function parameter schedule graph
46
0: Continue running
1: Shut down according to stopping mode
2: Loop length control
Thousands digit: Software reset length (could be
cleared by communication)
0: No operation
1: The current length is cleared
2:The current length and total length both cleared
F13.14 Record length manage Units digit: Stops the current length
0: Automatically cleared
1: Length is maintained
Tens digit: Power-down length memory setting
0: Not stored
1: Stored
Hundreds digit: length calculation at shutdown
0: The length is not calculated
1: Calculate the length
0 011
○
F14
-
Vector Control Parameter Group
Function
code
Name
Set range
Min.
unit
Factory
default
Modifi
-cation
F14.00 Speed/torque
control
selection
0: Speed control
1: Torque control (This parameter is valid when
F00.24=1 or 2)
1 0
○
F14.01 Speed
loop
high
speed proportional
gain
0.1
~
40.0 ( This parameter is valid when F00.24=1
or 2)
0.1 20.0
○
F14.02 Speed
loop
high
speed integral time
0.001
~
10.000s (This parameter is valid when
F00.24=1 or 2)
0.001s
0.040s
○
F14.03 Speed
loop
low
speed
proportional gain
0.1
~
80.0 ( This parameter is valid when F00.24=1
or 2)
0.1 20.0
○
F14.04 Speed
loop
low
speed
integral time
0.001
~
10.000s (This parameter is valid when
F00.24=1 or 2)
0.001s
0.020s
○
F14.05 Speed
loop
parameter
switching frequency
0.00Hz
~
20.00Hz (This parameter is valid when
F00.24=1 or 2)
0.01Hz 5.00Hz
○
F14.06 Low
frequency
power
generation stability
coefficient
0
~
50 (This parameter is valid when F00.24=1)
1
25
○
F14.07 Current
loop
proportional gain
1
~
500 (This parameter is valid when F00.24=1
or 2)
1 70
○
F14.08 Current
loop
integral
time
0.1
~
100.0ms (This parameter is valid when
F00.24=1 or 2)
0.1ms
4.0ms
○
F14.09 Motor-driven
torque
current limit value
0.0
~
250.0% (This parameter is valid when
F00.24=1 or 2 or 3)
0.1%
160.0%
○
F14.10 Braking
torque
current limit value
0.0
~
250.0% (This parameter is valid when
F00.24=1 or 2)
0.1%
160.0%
○
F14.11
Asynchronous motor
flux-weakening
control coefficient
20.0
~
100.0%(This parameter is valid when
F00.24=1 or 2)
0.1%
80.0%
○
F14.13 Torque
reference
and
limit channel
selection
Units digit: Torque provision channel selection
0: Digital setting
1: AI1 Analog setting
2: AI2 Analog setting
3: Terminal UP/DOWN adjustment setting
4: communication provision(Communication
address:1D01)
1 000
○