Function parameter schedule graph
28
3: Degression torque curve 3 (1.2 power)
4: User self-defined setting V/F curve
(Confirmed by F03.04~F03.11)
5:V/F Separation control (Voltage channel is
determined by F18.22)
F03.01 Torque boost mode
0: Manual boost.
1: Auto torque boost
1 0
○
F03.02 Torque
boost
0.0
~
12.0% 0.1%
Base
on
motor
type
○
F03.03 Torque boost cut-off
frequency
0.0
~
100.0%(Motor rated frequency)
0.1%
100.0%
○
F03.04 V/F frequency value 0
0.00
~
V/F frequency value 1
0.01Hz 10.00Hz
×
F03.05 V/F voltage value 0
0.00
~
V/F voltage value 1
0.01% 20.00%
×
F03.06 V/F frequency value 1
V/F frequency value 0
~
V/F frequency value 2 0.01Hz 20.00Hz
×
F03.07 V/F voltage value 1
V/F voltage value 0
~
V/F voltage value 2
0.01% 40.00%
×
F03.08 V/F frequency value 2
V/F frequency value 1
~
V/F frequency value 3 0.01Hz 25.00Hz
×
F03.09 V/F voltage value 2
V/F voltage value 1
~
V/F voltage value 3
0.01% 50.00%
×
F03.10 V/F frequency value 3
V/F frequency value 2
~
upper limit frequency
0.01Hz 40.00Hz
×
F03.11 V/F voltage value 3
V/F voltage value 2
~
100.00% (motor rated
voltage)
0.01% 80.00%
×
F03.12 V/F
oscillation
suppression factor
0
~
255 1
10
○
F04
-
Auxiliary running parameter group
Function
code
Name
Set range
Min.
unit
Factory
default
Modifi
-cation
F04.00 Jump freq. 1
0.00Hz
~
Upper limit frequency
0.01Hz
0.00Hz
×
F04.01 Jump freq. 1 range
0.00Hz
~
Upper limit frequency
0.01Hz
0.00Hz
×
F04.02 Jump freq. 2
0.00Hz
~
Upper limit frequency
0.01Hz
0.00Hz
×
F04.03 Jump freq. 2 range
0.00Hz
~
Upper limit frequency
0.01Hz
0.00Hz
×
F04.04 Jump freq. 3
0.00Hz
~
Upper limit frequency
0.01Hz
0.00Hz
×
F04.05 Jump freq. 3 range
0.00Hz
~
Upper limit frequency
0.01Hz
0.00Hz
×
F04.06 Slip freq. gain
0.0
~
300.0% 0.1%
0.0%
×
F04.07 Slip
compensation
limit
0.0
~
250.0% 0.1%
100.0%
×
F04.08 Slip
compensation
time constant
0.1
~
25.0s 0.1s
2.0s
×
F04.09 Carrier
freq.
0.5
~
16.0K 0.1K
Based
on
motor
type
○
F04.10 PWM
optimized
adjustment
Units digit: Carrier freq. is adjusted automatically
according to temperature
0: Banned.
1: Allowed.
Tens digit: low speed carrier freq. limit mode
0: No limit.
1: Limit.
Hundreds digit: carrier wave modulation system
0: 3 phase modulation.
1: 2 phase and 3 phase modulation.
Thousands digit: Asynchronous modulation:
synchronization mode (valid under V/F control)
0:Asynchronous modulation.
1:Synchronous modulation (under 85Hz:
1 0010 ×
ENC