Function parameter schedule graph
25
setup
F01.05 Auxiliary
frequency digital
control
Units digit: power down reserve setup
0:Auxiliary frequency power down reserve.
1:Auxiliary frequency power down no reserve.
Tens digit: halt reserve setup
0:Halt auxiliary frequency hold.
1:Halt auxiliary frequency recovery parameter F01.04
1 11
○
F01.06 Main and auxiliary
provide calculating
setup
0:Main frequency (complex frequency of current is
main frequency).
1: Auxiliary frequency(complex frequency of current is
auxiliary frequency.)
2: Plus(polarity oppose of complex and main
frequency,complex frequency is zero).
3:Minus(polarity oppose of complex and auxiliary
frequency,complex frequency is zero).
4:Multiplication(polarity opposed of main and
auxiliary frequency: complex frequency is zero).
5:Max(the max frequency of main and auxiliary
absolute value).
6:Min(the min frequency of main and auxiliary
absolute value).
7:Selection no-zero value(auxiliary is not negative,
main frequency prior
;
auxiliary is negative,complex
frequency is zero).
8:main frequency×Auxiliary frequency×2/F01.11
(polarity opposed of main and auxiliary frequency,
complex frequency is zero)
1 0
○
F01.07 Auxiliary
frequency provide
coefficient
0.00
~
10.00 0.01
1.00
○
F01.08 Coefficient
after
complex of main
and auxiliary
frequency
0.00
~
10.00 0.01
1.00
○
F01.09 Auxiliary
frequency range
selection
0:Relative upper limit frequency.
1:Relative main frequency.
1 0
○
F01.10 Auxiliary
frequency source
scope
0.00
~
1.00 0.01
1.00
○
F01.11 Upper
limit
frequency
Low limit frequency
~
600.00Hz 0.01Hz 50.00Hz
×
F01.12 Low
limit
frequency
0.00Hz
~
upper limit frequency
0.01Hz 0.40Hz
×
F01.13 Low
limit
frequency run
mode
0:As low limit frequency run.
1:As setting frequency run.
2:As zero frequency run.
3:Sleep: PWM clocked at sleep mode.
1 2 ×
F01.14 Sleep run hysteresis
frequency
0.01Hz
~
upper limit frequency(This function can be
used to finish the sleep mode function, realizing
energy-saving operation process, and the hysteresis
width can avoid inverter starting frequently in
threshold)
0.01Hz 0.01Hz
○
F01.15 Run
command
channel selection
0:Operation keyboard run control.
1:Terminal run command control
2:Communication run command control.
1 0
○
F01.16 Run direction setup Units digit: Keyboard command for/rev setup (only
1
1000
○