©2020 EMS Ltd. All rights reserved. Page 66 of 80
MK067-0001-99 (Issue 1) 04/11/2020 AJM
WZM Settings
Panel Type
Sounder Options
Device Indicator *
Conventional
Addressable
Default Tone Select
Sounder Duration
Sounder Activation
Pulsed Output
Off When Silenced
Off When Reset
WZM settings
The ‘WZM settings’ menu allows an engineer to program various WZM options. The available options are
explained in more detail below.
* Option only available
when ‘Panel Type’ is
set to ‘Addressable’
Panel type
This menu option changes the operation of the WZM; to work in conjunction with either a conventional fire
control panel, or an addressable fire control panel. The default setting is ‘Conventional’.
The LCD front display will state whether conventional mode or addressable mode is selected.
Sounder Options
The operation of the wireless sounders to be programmed in this menu. Available options are as follows:
Default Tone Select
This menu option allows the selection of the default sounder fire alarm tone.
Sounder Duration
This menu option allows has two available options. They are as follows:
Continuous ‘Upon a fire event, wireless sounders will continue to ring, until they are silenced.
30 Min Cut Off ’Upon a fire event, wireless sounders will be automatically switch off after 30 minutes,
to conserve battery life. Subsequent fire alarm activations will re-activate the sounders.
The default setting is 30 min cut off.