Input / output devices
Input / output devices have two resistor monitored fire inputs and two fire relay outputs. Both fire relay
outputs are rated 1 A at 30 VDC.
The device’s two relay outputs are programmable. Upon a fire condition, both outputs will automatically
change state. The outputs can be independently programmed to return to their normal state upon either,
when the control panel’s ‘Silence’ button is pressed, or when the control panel’s ‘Reset’ button is pressed.