©2020 EMS Ltd. All rights reserved. Page 67 of 80
MK067-0001-99 (Issue 1) 04/11/2020 AJM
WZM MENUS
Sounder Activation
As default, the WZM’s wireless sounders will only operate upon the WZM’s Fire Input being triggered. This
however can be changed, so that sounders operate, upon the activation of one of the WZM’s wireless
devices.
Pulsed Output
This menu option allows has two available options. They are as follows:
Fire Relay ‘Allows the relay output to change state upon a fire event for a preset period of time.
Available durations in seconds are 0 (output off ), or 5-60 seconds (in 5 second increments).
Fault Relay ‘Allows the relay output to change state upon a fault event for a preset period of time.
Available durations in seconds are 0 (output off ), or 5-60 seconds (in 5 second increments).
The default setting is 0 seconds (output off).
Device Indicator
This menu allows the programming of the wireless devices alarm indicator led operation. If the devices led
operation is required to be controlled by a separate Reset input (Input 2) then this function should be
selected (EN requirement). A change of state will be required on Input 2 when the system is reset. This will
allow the Wireless Zone Monitor to send a reset signal to the wireless devices to extinguish their alarm
indicator LED’s if they have been triggered.
Off When Silenced
This menu allows the method of control for the wireless devices individual alarm indicator to be selected.
The options are for the devices indicator which has alarmed and is in the on state to turn off on receipt of a
SILENCE command signal. This is generated when the fire input clears (Input 1) and will therefore work the
same as sounders on the Zone Monitor.
Off When Reset
This menu allows the method of control for the wireless devices individual alarm indicator to be selected.
Alternatively the devices indicator can be selected so it extinguishes only after a RESET command (Input 2
clear) has been activated. This requires a reset input wired from the control panel to Input 2 on the Wireless
Zone Monitor. When this input is activated and subsequently clears a reset signal can be sent. This can be
therefore be wired into a relay which changes state on a reset event or returns to a normal state when the
panel is reset. The default operation is to turn off on a Silence command when the fire input clears (Input 1).