background image

19562-3-0907

Page 10

Installing Wall Bracket (Figures 5 and 6)

After finding a location for the furnace, gas supply and vent, the 

wall bracket must be positioned and installed.  The bracket should 

be mounted to the wall studs, if possible, or anchored solidly to the 

wall.  Use the (2) 10 x 1" (25mm) hex-head screws or (2) plastic 

anchors provided.  Drill (2) 5/16" (8mm) diameter holes in wall if 

plastic anchors are used.  Attach the two wall mounting brackets 

to the casing back by using (4) 10 x 1/2" (13mm) hex-head screws 

provided.

 Figure 5

WALL

CASING

BACK

#10 X 1"

WALL MOUNTING BRACKET

WALL

BRACKET

#10 X 1/2"

#10 X 1/2"

4" (102mm)

 Figure 6

WALL

INTAKE FLEX HOSE

WITH CLAMPS

EXHAUST

INTAKE AIR

MOUNTING PLATE

EXHAUST ELBOW MAY

BE CUT TO LENGTH

TO FIT VENT BOX.

SECURE IN PLACE

USING HOSE CLAMPS

PROVIDED.

KEEP CAP ON

UN-USED AIR

INTAKE OPENING

Figure 7

EXHAUST AIR

ORANGE SILICONE

ELBOW CONNECTOR

INTAKE AIR

BLACK FLEXIBLE HOSE

Figure 8

Figure 9

Venting (Figures 7, 8 and 9)

This unit is vented directly out the back using the concentric vent 

tube assembly provided. See Figure 2 for vent hole location. This 

hole location can be conveniently moved closer to unit exhaust 

outlet tube to avoid wall stud interference if necessary. The orange 

silicone exhaust elbow would need to be cut to length. Do not 

locate vent directly behind the exhaust outlet. Do not use the orange 

silicone elbow for extended vent runs where the  possibility of 

flue condensate exists unless the run is horizontal and the elbow is 

sloped downward away from the heater. See Figure 12 for extended 

vertical venting.
The vent provided will accommodate walls up to 10" thick and 

can be cut shorter for thinner walls if desired by using a hacksaw 

or cut-off saw. Be sure to leave the minimum 3/4" of tube length 

extending beyond the outside wall plate. Both the inner and outer 

tube will be cut to the same length as the inner exhaust tube has an 

extension piece which is added during final outside assembly.

VENT TUBING

SILICONE COUPLING

HOSE CLAMP

HOSE CLAMP

EDGE

EXHAUST CONNECTIONS

INTAKE FLEX HOSE CONNECTION

WITH INTERNAL METAL COUPLING

VENT COUPLING CONNECTIONS

EXTENDED VENT

Summary of Contents for DV-20E

Page 1: ...Series in Canada This appliance is only for use with the type s of gas indicated on the rating plate A conver sion kit is supplied with the appliance Installer Leave this manual with the appli ance C...

Page 2: ...nts for Massachusetts 5 Introduction 6 Speci cations 6 Gas Supply 7 Gas Conversion Instructions 8 Clearances 9 Furnace Installation 9 12 Lighting Instructions 13 Wiring 14 Maintenance 15 Operation and...

Page 3: ...on and repair should be done by a QUALIFIED SERVICE PERSON The appliance should be inspected before use and at least annually by a quali ed service person More frequent cleaning may be required due to...

Page 4: ...ot lights perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorpt...

Page 5: ...iredinaccordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certi ed 3 SIGNAGE Ametalorplasticidenti cationplateshallbe permanently mounted to the exterior...

Page 6: ...corporationorcompanywhicheitherin person or through a representative is engaged in and is responsible for a the installation or replacement of gas piping or b the connection installation repair or ser...

Page 7: ...ped or plugged for pressure test Never pressure test with appliance connected control valve will sustain damage A gas valve and ground joint union should be installed in the gas line upstream of the g...

Page 8: ...s conversion label are provided in conversion kit attached to manifold pipe 1 Make sure gas supply to furnace is off prior to conversion and disconnect electrical power to unit 2 Open brass union loca...

Page 9: ...uld be a minimum horizontal distant of six 6 feet 1 83m from any pressure regulator In case of regulator malfunction the six 6 feet 1 83m distance will reduce the chance of gas entering the vent cap I...

Page 10: ...it is vented directly out the back using the concentric vent tube assembly provided See Figure 2 for vent hole location This hole location can be conveniently moved closer to unit exhaust outlet tube...

Page 11: ...d conform to ASTM Standard D2564 for PVC or D2235 for ABS This PVC or ABS pipe must not be used for the exhaust vent pipe run Note Type SDR pipe is not approved for use in Canada For new construction...

Page 12: ...the condensate drain pan located within the appliance Whenever a horizontal vent run is used where local codes allow you can slope the exhaust pipe downward to the outside 1 4 6mm per foot 305mm The d...

Page 13: ...ance and to replace any part of the control system and any gas control which has been under water 1 STOP Read the safety information above 2 Set the thermostat to lowest setting 3 Turn off all electri...

Page 14: ...alled turn off gas supply and electric supply 2 Remove casing front 3 Remove black hose from front nipple on pressure switch 4 Remove junction box cover 4 screws 5 Please refer to wiring diagram for r...

Page 15: ...and then turn temperature control knob clockwise slowly till furnace turns on For typical room comfort the control knob should be pointed toward medium 2 The furnace control board follows sequence of...

Page 16: ...lashes Pressure switch is closed with inducer off Check Pressure Switch and Replace 4 Flashes Lockout due to failed ignition Check for Broken Ignitor Check for Bent Ignitor Bracket Ignitor too far fro...

Page 17: ...d the Description of each part from the following appropriate illustration and list Be sure to give all this information Furnace Model Number Part Description Furnace Serial Number Part Number Type of...

Page 18: ...19562 3 0907 Page 18 PARTS VIEW...

Page 19: ...19562 3 0907 Page 20 Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 PH 618 233 7420 or 800 851 3153 FAX 618 233 7097 or 800 443 8648 info empirecomfort com www empirecomfort com...

Reviews: