background image

19562-3-0907

Page 12

Figure 11

Condensate Removal (Figures 11 and 12)

The condensate drain kit is used in conjunction with DVE and 

DVE-2, intake/exhaust extension kits.  The condensate drain kit is 

required whenever there is a vertical vent run, in a heated room [10 

ft. (3m) or more for DV-40E or 6 ft. (1.8m) or more for DV-20E], 

in the intake/exhaust venting. 
Whenever a vertical vent run, in a heated room [10 ft. (3m) or more 

for DV-40E or 6 ft. (1.8m) or more for DV-20E] and a horizontal 

vent run are combined, you must purchase the optional condensate 

drain kit, part number DV-1108.  If the vertical vent run lengths are 

less than those required for the condensate drain kit, you can slope 

the horizontal vent run portion, downward 1/4" (6mm) per foot 

(.3m) to the outside.  However, if local codes prohibit condensate 

from draining outside and the appliance produces condensate, the 

horizontal portion of the vent run must slope downward, to the 

appliance, 1/4" (6mm) per foot (.3m).  This will allow any condensate 

to flow into the condensate drain kit.  Do not use the orange silicone 

elbow supplied with unit to catch condensate. You can route the 

condensate from the condensate drain kit to an existing drain or 

into the condensate drain pan located within the appliance.
Whenever a horizontal vent run is used, where local codes allow, 

you can slope the exhaust pipe downward, to the outside, 1/4" 

(6mm) per foot (305mm).  The downward slope on the exhaust 

pipe will allow any condensate to flow out of the exhaust pipe.  If 

local codes prohibit condensate from draining to the outside and 

the appliance produces condensate you must purchase condensate 

drain kit, part number DV-1108.

INTAKE

SLOPE THE VENT TERMINAL

HORIZONTAL RUN DOWNWARD

THE OUTSIDE TO DRAIN OUT

ANY CONDENSATE

EXHAUST

VENT TERMINAL

EXHAUST AIR

ELBOW WITH CLAMPS

INTAKE AIR

SUPPORT STAP EVERY

5 FT. (1.5m) MIN.

SHROUD SIDE

EXHAUST AIR

INTAKE AIR

EXTERIOR

W

ALL

COUPLING WITH

HOSE CLAMPS

SLOPE DOWNWARD 1/4" (6mm)

PER FOOT (m) TO DRAIN ANY

CONDENSATE OUTSIDE

FILTER

TEMPERATURE CONTROL DOOR

INTERIOR WALL

Figure 12

Reassembly and Resealing Vent-Air  Intake System

When vent-air intake system is removed for servicing the furnace, 

the following steps will assure proper reassembly and resealing 

of the vent-air intake assembly.  Be sure all hose connections and 

elbow assemblies are re-secured in place using the hose clamps 

removed.  Reattach all screws securing mounting flanges and inspect 

all connections for a tight fit.  Use high temperature silicone caulk 

rated at 204°C/400°F to reseal the inlet air vent pipe and exhaust 
air vent pipe to the mounting plate.

Summary of Contents for DV-20E

Page 1: ...Series in Canada This appliance is only for use with the type s of gas indicated on the rating plate A conver sion kit is supplied with the appliance Installer Leave this manual with the appli ance C...

Page 2: ...nts for Massachusetts 5 Introduction 6 Speci cations 6 Gas Supply 7 Gas Conversion Instructions 8 Clearances 9 Furnace Installation 9 12 Lighting Instructions 13 Wiring 14 Maintenance 15 Operation and...

Page 3: ...on and repair should be done by a QUALIFIED SERVICE PERSON The appliance should be inspected before use and at least annually by a quali ed service person More frequent cleaning may be required due to...

Page 4: ...ot lights perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorpt...

Page 5: ...iredinaccordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certi ed 3 SIGNAGE Ametalorplasticidenti cationplateshallbe permanently mounted to the exterior...

Page 6: ...corporationorcompanywhicheitherin person or through a representative is engaged in and is responsible for a the installation or replacement of gas piping or b the connection installation repair or ser...

Page 7: ...ped or plugged for pressure test Never pressure test with appliance connected control valve will sustain damage A gas valve and ground joint union should be installed in the gas line upstream of the g...

Page 8: ...s conversion label are provided in conversion kit attached to manifold pipe 1 Make sure gas supply to furnace is off prior to conversion and disconnect electrical power to unit 2 Open brass union loca...

Page 9: ...uld be a minimum horizontal distant of six 6 feet 1 83m from any pressure regulator In case of regulator malfunction the six 6 feet 1 83m distance will reduce the chance of gas entering the vent cap I...

Page 10: ...it is vented directly out the back using the concentric vent tube assembly provided See Figure 2 for vent hole location This hole location can be conveniently moved closer to unit exhaust outlet tube...

Page 11: ...d conform to ASTM Standard D2564 for PVC or D2235 for ABS This PVC or ABS pipe must not be used for the exhaust vent pipe run Note Type SDR pipe is not approved for use in Canada For new construction...

Page 12: ...the condensate drain pan located within the appliance Whenever a horizontal vent run is used where local codes allow you can slope the exhaust pipe downward to the outside 1 4 6mm per foot 305mm The d...

Page 13: ...ance and to replace any part of the control system and any gas control which has been under water 1 STOP Read the safety information above 2 Set the thermostat to lowest setting 3 Turn off all electri...

Page 14: ...alled turn off gas supply and electric supply 2 Remove casing front 3 Remove black hose from front nipple on pressure switch 4 Remove junction box cover 4 screws 5 Please refer to wiring diagram for r...

Page 15: ...and then turn temperature control knob clockwise slowly till furnace turns on For typical room comfort the control knob should be pointed toward medium 2 The furnace control board follows sequence of...

Page 16: ...lashes Pressure switch is closed with inducer off Check Pressure Switch and Replace 4 Flashes Lockout due to failed ignition Check for Broken Ignitor Check for Bent Ignitor Bracket Ignitor too far fro...

Page 17: ...d the Description of each part from the following appropriate illustration and list Be sure to give all this information Furnace Model Number Part Description Furnace Serial Number Part Number Type of...

Page 18: ...19562 3 0907 Page 18 PARTS VIEW...

Page 19: ...19562 3 0907 Page 20 Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 PH 618 233 7420 or 800 851 3153 FAX 618 233 7097 or 800 443 8648 info empirecomfort com www empirecomfort com...

Reviews: