background image

19562-3-0907

Page 15

  The hot surface ignitor is energized and after a 17 second warm-

up, the gas valve circuit is energized, opening the gas valve 

and igniting the burners.   After burning for about 30 seconds, 

the  circulating  air  blower  comes  on,  delivering  warm  air  to 

the room.  If ignition does not occur, the ignition sequence is 

repeated again up to 2 more times. (3 trials for ignition-total)

3.  After the furnace operates and satisfies the thermostat, the gas 

valve closes and the circulating air blower continues to run for 

about 2 minutes and then shuts off.  The inducer blower runs 

for 5 seconds and shuts off.

  If for any reason ignition and operation does not occur, the 

control board will blink the red fault status LED, a sequence 

code, indicating what to look for as a troubleshooting guide.   

If the red LED is ON but not blinking check the electronic 

temperature control to verify its operation. This can be easily done 

by disconnecting the 3 electronic temperature control leads from 

the main furnace board and using a pig tail jumper to connect 

R & W together on the board. If the furnace comes on and runs 

normally the temperature control board is malfunctioning. If 

the heater still does not come on, then the main furnace board 

is malfunctioning. Look for any fault codes below and verify 

the 3 amp fuse is not blown.

Your  new  furnace  should  provide  many  years  of  trouble  free 

performance, however, a yearly inspection of the burners , flue 

passageways and the outlet vent assembly should be done.  Be 

sure all passageways are open and clear of any obstruction, or soot 

build up.  Be sure to shut off all power to the unit while performing 

this inspection.  
Periodically remove the circulating air filter and clean with water 

to remove all dirt.  Shake dry and reinstall in unit.

System Operation

1.  This furnace has an electronic thermostat and control board 

to monitor the room temperature and then control the furnace 

operation to provide the best comfort and performance from a 

heating appliance.  To operate unit turn ON/OFF switch to ON 

and then turn temperature control knob clockwise slowly till 

furnace turns on.  For typical room comfort, the control knob 

should be pointed toward medium.

2.  The furnace control board follows sequence of operation which 

allows for self diagnosis in the event there is a problem.  The 

control then blinks a status light, a set number of blinks based 

on what problem has been encountered.  When the furnace is 

on and there is a no fault condition, the red LED is on.

  On a typical call for heat by the integral thermostat 24 VAC is 

applied to the W terminal on the board.   

  The inducer blower circuit is energized and the inducer blower 

comes on for 15 seconds pre-purging out any gas and closing 

the pressure switch.

Proper Main Burner Flame

The proper main burner flame will be a blue primary (inner) flame 

with a larger, lighter blue secondary (outer) blue flame.

Figure 13

Cleaning Main Burner(s)

Remove main burner(s) and apply air pressure inside the throat and 

ports of the main burner(s).

Removing Main Burner(s)

1.  Remove front grill assembly.

2.  Remove burner compartment access panel (2 screws).

3.  Remove main burner(s) from burner compartment (2 screws 

per main burner).

Removing Gas Valve

1.  Remove front grill assembly.

2.  Disconnect manifold union assembly at gas valve.

3.  Remove (2) two 24 volt wires from gas valve.  Label wires prior 

to disconnection from gas valve.

4.  Remove gas valve from gas valve bracket.

Removing Main Burner Orifice(s

)

1.  Remove front grill assembly.

2.  Remove burner compartment access panel (2 screws).

3.  Disconnect manifold union assembly.

4.  Disconnect manifold union assembly brackets (5 screws).

Removing Ignitor and Flame Sensor

1.  Remove front grill assembly.

2.  Remove ignitor from burner compartment (2 screws).

3.  Remove flame sensor from burner compartment (1 screw).

Cleaning Combustion (Exchanger) Assembl

y

A  QUALIFIED  SERVICE  PERSON  should  remove  the 

combustion  (exchanger)  assembly.    Apply  air  pressure  to  the 

inside of the combustion (exchanger) assembly in order to clear 

all passageways.

Oiling

The blower motor has an oil hole located on each end of the motor.  

Use #20 motor oil only.   It is best to oil the motor several times 

during the heating season using 2 or 3 drops each time.

MAINTENANCE

OPERATION AND TROUBLESHOOTING

Summary of Contents for DV-20E

Page 1: ...Series in Canada This appliance is only for use with the type s of gas indicated on the rating plate A conver sion kit is supplied with the appliance Installer Leave this manual with the appli ance C...

Page 2: ...nts for Massachusetts 5 Introduction 6 Speci cations 6 Gas Supply 7 Gas Conversion Instructions 8 Clearances 9 Furnace Installation 9 12 Lighting Instructions 13 Wiring 14 Maintenance 15 Operation and...

Page 3: ...on and repair should be done by a QUALIFIED SERVICE PERSON The appliance should be inspected before use and at least annually by a quali ed service person More frequent cleaning may be required due to...

Page 4: ...ot lights perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorpt...

Page 5: ...iredinaccordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certi ed 3 SIGNAGE Ametalorplasticidenti cationplateshallbe permanently mounted to the exterior...

Page 6: ...corporationorcompanywhicheitherin person or through a representative is engaged in and is responsible for a the installation or replacement of gas piping or b the connection installation repair or ser...

Page 7: ...ped or plugged for pressure test Never pressure test with appliance connected control valve will sustain damage A gas valve and ground joint union should be installed in the gas line upstream of the g...

Page 8: ...s conversion label are provided in conversion kit attached to manifold pipe 1 Make sure gas supply to furnace is off prior to conversion and disconnect electrical power to unit 2 Open brass union loca...

Page 9: ...uld be a minimum horizontal distant of six 6 feet 1 83m from any pressure regulator In case of regulator malfunction the six 6 feet 1 83m distance will reduce the chance of gas entering the vent cap I...

Page 10: ...it is vented directly out the back using the concentric vent tube assembly provided See Figure 2 for vent hole location This hole location can be conveniently moved closer to unit exhaust outlet tube...

Page 11: ...d conform to ASTM Standard D2564 for PVC or D2235 for ABS This PVC or ABS pipe must not be used for the exhaust vent pipe run Note Type SDR pipe is not approved for use in Canada For new construction...

Page 12: ...the condensate drain pan located within the appliance Whenever a horizontal vent run is used where local codes allow you can slope the exhaust pipe downward to the outside 1 4 6mm per foot 305mm The d...

Page 13: ...ance and to replace any part of the control system and any gas control which has been under water 1 STOP Read the safety information above 2 Set the thermostat to lowest setting 3 Turn off all electri...

Page 14: ...alled turn off gas supply and electric supply 2 Remove casing front 3 Remove black hose from front nipple on pressure switch 4 Remove junction box cover 4 screws 5 Please refer to wiring diagram for r...

Page 15: ...and then turn temperature control knob clockwise slowly till furnace turns on For typical room comfort the control knob should be pointed toward medium 2 The furnace control board follows sequence of...

Page 16: ...lashes Pressure switch is closed with inducer off Check Pressure Switch and Replace 4 Flashes Lockout due to failed ignition Check for Broken Ignitor Check for Bent Ignitor Bracket Ignitor too far fro...

Page 17: ...d the Description of each part from the following appropriate illustration and list Be sure to give all this information Furnace Model Number Part Description Furnace Serial Number Part Number Type of...

Page 18: ...19562 3 0907 Page 18 PARTS VIEW...

Page 19: ...19562 3 0907 Page 20 Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 PH 618 233 7420 or 800 851 3153 FAX 618 233 7097 or 800 443 8648 info empirecomfort com www empirecomfort com...

Reviews: