35919-4-1015
Page 18
INSTALLATION (continued)
Vent Pipe Clearance
For horizontal vent, maintain a minimum 2-in clearance to the bottom
and sides of the vent, and 3-in clearance to combustibles above
the vent pipe.
See Figure 30.
VENT PIPE
2” MINIMUM CLEARANCE AROUND VENT PIPE
Figure 29
Top of
Vent
3” (75mm)
2” (50mm)
2” (50mm)
7” Diameter
intake vent
4” Diameter flue
Combustibles NOT
allowed in shaded
area
Figure 30
Framing - In the Wall
Fireplace framing can be built before or after the fireplace is set
in place. Framing should be positioned to accommodate wall
covering and fireplace facing material. The fireplace framing should
be constructed of 2 x 4 lumber. Refer to
Figure 31
for minimum
framing dimensions.
CAUTION
CAUTION: MEASURE FIREPLACE DIMENSIONS AND VERIFY
FRAMING METHODS, AND WALL COVERING DETAILS
BEFORE FRAMING CONSTRUCTION BEGINS.
Note
: For finishing to top of fireplace, refer to
Figure 32.
Note
: Minimum chase top to top of framing edge is 24-in.
DVCP32
DVCP36
DVCP42
(Dimensions in inches)
A
47-1/4
47-1/4
49-1/4
B
34-3/4
37-3/4
43-3/4
C
17-1/4
17-1/4
17-1/4
Figure 31
Finishing
Finish the walls with the material of your choice.
Figure 19
on
page 13 shows the minimum vertical and corresponding maximum
horizontal dimensions of mantels or other combustible projections
above the top front edge of the fireplace.
Only non-combustible materials may be used to cover the black
fireplace front.
WARNING
When finishing the fireplace never obstruct or modify the air
inlet/outlet in any manner. Provide adequate clearances around
air openings into the combustion chamber.
CAUTION
If the joints between the finished wall and the fireplace surround
(top and sides) are sealed, a 300 Degree F minimum sealant mate-
rial must be used. These joints are not required to be sealed. Only
non-combustible material (using 300 Degree F minimum adhesive
if needed), can be applied as facing to the fireplace surround.