Document Part # 026-4275 Rev 0
Page 4 of 23
©2019 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emerson.com for the latest technical documentation and updates.
E2 Serial Port Setup
1. Log into the E2 by pressing the
button
and enter “USER” for
Username
and “PASS”
for
Password
, then press
.
2. Press
,
,
,
to go to
General
Controller Info
.
3. Press
twice to move to the
C3: Serial
tab.
4. Press
to highlight the
Com6 Connection
value.
5. Press
(LOOK UP)
and select
MODBUS-1
(if
MODBUS-
1 is being used, select
MODBUS-2
or
MODBUS-3
connection), then
press
to set configuration.
6. Press
to select options and set the
MODBUS connection as follows:
7. Press
to set configuration and
to
save the changes.
8. Press
to return to the
Home screen
.
Note: The XM670K MODBUS Connection must be set to
9600 baud.
Adding a XM670K_50 Controller in E2
1. Press
,
,
,
to enter
Connected I/O
Boards and Controllers
.
2. Press
once to move to
C4: Third Party
tab. Highlight the
XM670K_50
application
and enter the desired number of devices
under
Quantity
.
3. Press
to save changes and
to
return to the
Home screen.
Commissioning XM670K_50 Controller
1. Press
,
,
,
to enter the
Network
Summary screen
.
2. Highlight the XM670K_50 controller to be
commissioned by pressing the
arrow key
then
Figure 12 - Serial Tab
Com6 Baud:
9600
Com6 Data Size:
8
Com 6 Parity:
None
Com 6Stop Bits:
1
Figure 13 - Third Party Tab