![Emerson XM670K 50 Quick Start Manual Download Page 15](http://html.mh-extra.com/html/emerson/xm670k-50/xm670k-50_quick-start-manual_101394015.webp)
Document Part # 026-4275 Rev 0
Page 15 of 23
©2019 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emerson.com for the latest technical documentation and updates.
PRB3 ALM
Reports status of probe 3
alarm if used
Reports as
ON
if probe 3 is in error. A probe that is shorted or open will
cause this to alarm and to be on and will show on the device application
status screen in the probe box. The local display will flash
P3
. Once the
probe has been repaired, the device will stop the alarm immediately. This
alarm can be disabled from reporting to the E2 advisory log or set to
Notice
, and the priority level can be set.
PRB4 ALM
Reports status of probe 3
alarm if used
Reports as
ON
if probe 3 is in error. A probe that is shorted or open will
cause this to alarm and to be on and will show on the device application
status screen in the probe box. The local display will flash
P3
. Once the
probe has been repaired, the device will stop the alarm immediately. This
alarm can be disabled from reporting to the E2 advisory log or set to
Notice
, and the priority level can be set.
TMP1 ALM LO
Reports low temperature
alarm 1 status
Reports as on if the configured
TMP1 ALRM PROBE (rAL)
falls below the
TMP1 ALARM LO (ALL)
setting after delay.
TempAlmStartDly dAO - Temp alarm delay
after startup
This setting delays the device alarm settings from alarming for the time
set after a power cycle or a transition from device OFF to device ON state.
TMP1 ALM HI
Reports high temperature
alarm 1 status
Reports as ON if the configured
TMP1 ALRM PROBE (rAL)
falls below the
TMP1 ALARM HI (ALU)
setting after delay.
TMP2 ALM LO
Reports low temperature
alarm 2 status
Reports as on if the configured
TMP2 ALRM PROBE (rA2)
falls below the
TMP2 ALARM LO (A2L)
setting after delay.
TMP2 ALM HI
Reports high temperature
alarm 2 status
Reports as on if the configured
TMP2 ALRM PROBE (rA2)
falls below the
TMP2 ALARM HI (A2U)
setting after delay.
DOOR OPEN
ALRAM
Reports door open alarm
status
Reports as ON if either Digital Input 1, Digital Input 2 or Digital Input 3 is
configured for the Door Switch and after the respective digital input delay
setting exceeded its time setting. This alarm will show as ON in the device
application Status screen in the General Status box. The state of this digital
output can be pointed to other E2 applications. The local display will flash
dA
. This alarm will stop immediately after the door switch has gone back
to its normal digital state. This alarm can be disabled from reporting to the
E2 advisory log or set to
Notice
, and the priority level can be set.
CMP1 ALM
Reports compressor 1
safety alarm status
Reports compressor 1 safety alarm status on the application Status
screen. Update rate 10 - 30 seconds. Can be pointed to for use in other
applications. Logging set by default. User can disable logging.
TempAlmDefDly
EdA - Temp alarm delay
after defrost
Sets the delay of a temperature alarm of either configured temperature
alarm directly after a defrost. This is added to the
TMP1 ALARM DELAY
(ALd)
or
TMP2 Alarm Delay (A2D)
.
CMP2 ALM
Reports compressor 2
safety alarm status
Reports compressor 2 safety alarm status on the application Status
screen. Update rate 10 - 30 seconds. Can be pointed out for use in other
applications. Logging set by default. User can disable logging.
ALARM
Reports alarm relay output
status
Reports as ON if any device alarm is generated. This alarm will show as ON
in the device application status screen in the General Status box. The state
of this digital output can be pointed to other E2 applications. The local
display will annunciate an alarm sound that can be silenced at either the
display itself by pressing any button or through the device application
commands navigated to by pressing Enter when on the device application
Status screen. This alarm can be disabled from reporting to the E2
advisory log or set to
Notice
, and the priority level can be set.
TempAlmDoorDly dot - Temp alarm delay
after door open
This setting delays the device temperature alarms from alarming for the
time set if the temperature exceeds the alarm settings when the door
switch has been activated.
Table 2 - XM670K_50 Property Help Explanations