5. ROCKWELL SOFTWARE PACKAGE
6/2022
Emerson.com/SolaHD
User Guide
A272-365
•
PS 1 & 2 Event 2 Type
•
PS 1 & 2 Event 2 Timestamp
5.3.4 MESSAGE GROUP 4: MSG_USER_PARAMETER_WRITE
The user will have the ability to enter the following data. Upon change of value in the UDT_Emerson_
SCM_HMI, the PLC will write the following class 3 data to the SCM upon input change:
•
PS 1 & 2 User Alarm Limit: Output Current High
•
PS 1 & 2 User Alarm Limit: Temperature High
•
PS 1 & 2 User Alarm Limit: Alarm Flag Enable
The PLC program will monitor the alarm flags from the SCM as class 1 data. If the alarms are triggered,
the PLC will set corresponding alarms in the PLC.