Page: 11
1. PRODUCT OVERVIEW
6/2022
Emerson.com/SolaHD
User Guide
A272-365
1.4 NETWORK AND MODULE STATUS INDICATORS
As shown in
Section 1.3
, there are two LED indicators on the SCM-E-EIP, one for Network and one for Module.
The table below defines the different status of both the Network and Module LED indicators compliant with
CIP Specification as stated in Volume 2:EtherNet/IP Adaptation of CIP, Chapters 9-4.2 and 9-4.3.
LED Indicator
LED State
Summary
Definition
Module
Steady Off
No power
No power is supplied to the SCM.
Steady Green
Device operational
SCM-E-EIP and Power Supplies
are operating correctly.
Flashing Green
Standby
The SCM is in the initialization state.
Flashing Red
Major Recoverable Fault
A Power Supply has a Major
Recoverable Fault.
Flashing Green / Red Self-test
SCM is performing a self-test.
Network
Steady Off
Not powered, no IP
address
The device is powered off, or is
powered on but with no IP address
configured.
Flashing Green
No connections
An IP address is configured, but no
CIP connections are established, and
an Exclusive Owner connection has
not timed out.
Steady Green
Connected
An IP address is configured, at least
one CIP connection is established,
and an Exclusive Owner connection
has not timed out.
Flashing Red
Connection timeout
An IP address is configured, and
an Exclusive Owner connection for
which this device is the target has
timed out.
Steady Red
Duplicate IP
The SCM has detected that its IP
address is already in use.
Flashing Green / Red Self-test
SCM is performing a self-test.