Page: 57
6. ADVANCED MONITORING SCENARIOS
6/2022
Emerson.com/SolaHD
User Guide
A272-365
UDT Element Name
Type
Attribute
Number
Description
iSCM_Configuration
Int
-
User input representing configuration
of power supplies
0 = no redundancy mode selected
1 = redundant supply mode
2 = increased power mode
PS1_High_Temp_Limit
UDT_Emerson_
Parameter
301
User input for high temperature limit in
degrees Celsius
PS2_High_Temp_Limit
UDT_Emerson_
Parameter
300
User input for high temperature limit in
degrees Celsius
PS1_High_Current_Limit
UDT_Emerson_
Parameter
317
User input for high current limit
in amps
PS2_High_Current_Limit
UDT_Emerson_
Parameter
316
User input for high current limit
in amps
bPS1_User_Alarm_EN
Bool
402
Enable/disable for
user-configured alarms
bPS2_User_Alarm_EN
Bool
403
Enable/disable for
user-configured alarms
rTotal_Current_Warning_
Limit
Real
-
User input for total current early
warning limit. This value will be
compared to the sum of the PS1’s and
PS2’s output current
rTotal_Current_Critical_
Alarm_Limit
Real
-
User input for the total current
critical alarm limit. This value will be
compared to the sum of the PS1’s and
PS2’s output current
rTotal_Output_Current
Real
-
Total output current of SDN1 and SDN2
rTime_On_Warning_Limit
Real
-
User input for the time-on early
warning alarm limit (in hours)
rTime_On_Critical_Alarm
_Limit
Real
-
User input for the time-on critical alarm
limit (in hours)