5.6
Functional check
Emerson calibrated the system at the factory for your specific gas or vapor detection
requirements. Use the check filters included in the commissioning kit according to the
corresponding calibrating gas to validate correct installation.
The functional check filter is a convenient operational check used to confirm that the
response has not changed from previous readings. The filter is not used for calibration,
which is unnecessary, nor does it equate to a particular quantity of gas.
Prerequisites
Note
This functional verification procedure is for a standard 0-20 mA output.
Prior to starting the functional check, verify that the power to the detector is on and that
the current of the 0-20 mA channel is stable. Record the reading.
Procedure
1. Position the functional check filter in front of the detector. Center the functional
check filter's window over the viewing window of the detector.
The check filters are provided in the commissioning kit.
Figure 5-5: Detector with functional check filter installed
2. Wait twenty seconds.
3. Read the 0-20 mA current. Determine the difference between the reading taken
with and without the functional check filter.
The difference is the 0-20 mA current variance.
4. Record the 0-20 mA current variance in the maintenance log book.
Postrequisites
If the variance is more than a 30 percent change when compared to the previous check
(see delivery form), repeat the alignment.
Reference Manual
Operation
00809-0100-4035
May 2022
Rosemount 935
45
Summary of Contents for Rosemount 935
Page 8: ...Product overview Reference Manual May 2022 00809 0100 4035 8 Emerson com Rosemount ...
Page 16: ...Technical description Reference Manual May 2022 00809 0100 4035 16 Emerson com Rosemount ...
Page 22: ...Operating modes Reference Manual May 2022 00809 0100 4035 22 Emerson com Rosemount ...
Page 46: ...Operation Reference Manual May 2022 00809 0100 4035 46 Emerson com Rosemount ...
Page 52: ...Troubleshooting Reference Manual May 2022 00809 0100 4035 52 Emerson com Rosemount ...
Page 56: ...Ordering information Reference Manual May 2022 00809 0100 4035 56 Emerson com Rosemount ...
Page 62: ...Specifications Reference Manual May 2022 00809 0100 4035 62 Emerson com Rosemount ...
Page 70: ...Wiring configurations Reference Manual May 2022 00809 0100 4035 70 Emerson com Rosemount ...
Page 74: ...Support Reference Manual May 2022 00809 0100 4035 74 Emerson com Rosemount ...