Fed directly from cells or batteries.
•
If the product is to be used as a safety related device, an appropriate independent
certification, would be required meeting all the requirements.
4.6
Installing conduits and cables
The conduit and cable installation must comply with the following guidelines:
•
To avoid water condensation in the detector, install it with the conduits/cable entries
facing downwards.
•
Use flexible conduits/cables for the last portion connecting to the detector.
•
When pulling the cables through the conduits, ensure that they are not tangled or
stressed. Extend the cables about 12 in (305 mm) beyond the detector location to
accommodate wiring after installation.
•
After pulling the conductor cables through the conduits, perform a continuity test.
Reference Manual
Installation
00809-0100-4035
May 2022
Rosemount 935
29
Summary of Contents for Rosemount 935
Page 8: ...Product overview Reference Manual May 2022 00809 0100 4035 8 Emerson com Rosemount ...
Page 16: ...Technical description Reference Manual May 2022 00809 0100 4035 16 Emerson com Rosemount ...
Page 22: ...Operating modes Reference Manual May 2022 00809 0100 4035 22 Emerson com Rosemount ...
Page 46: ...Operation Reference Manual May 2022 00809 0100 4035 46 Emerson com Rosemount ...
Page 52: ...Troubleshooting Reference Manual May 2022 00809 0100 4035 52 Emerson com Rosemount ...
Page 56: ...Ordering information Reference Manual May 2022 00809 0100 4035 56 Emerson com Rosemount ...
Page 62: ...Specifications Reference Manual May 2022 00809 0100 4035 62 Emerson com Rosemount ...
Page 70: ...Wiring configurations Reference Manual May 2022 00809 0100 4035 70 Emerson com Rosemount ...
Page 74: ...Support Reference Manual May 2022 00809 0100 4035 74 Emerson com Rosemount ...