11. Install a regulator on the target gas source.
12. Attach a length of calibration tubing (PVC tubing, 3/16-in. ID, 5/16-in. OD) from the
regulator on the target gas source to the IP filter inlet on the bottom of the sensor.
Reference Manual
Configuration
00809-0100-4928
September 2019
Rosemount 928
65