10. On the
Configure Process Alerts
screen, select
OK
to confirm successful process
alert configurations.
11. Repeat
as necessary to configure additional process alerts.
12. When you have completed configuration, remove the HART
®
communication leads
from the Comm terminals on the terminal block and replace the rear housing cover.
Configure process alerts using AMS Wireless Configurator
Procedure
1. On the
Guided Setup
tab, in the Optional Setup field, select
Configure Process
Alerts
.
The
Process Alerts
window is displayed.
Reference Manual
Configuration
00809-0100-4928
September 2019
Rosemount 928
45