If there is an immediate alarm
WARNING
Alarm
If the device joins the network and immediately issues an alarm, respond as though the
alarm is real until it is proven false.
If the alarm is false, it is likely due to sensor configuration. Verify the sensor configuration,
alert set points, and alarm set points.
4.7
Troubleshoot communication
If the device is not joined to the network after power up, verify the correct configuration of
the network ID and join key and verify that active advertising has been enabled on the
wireless gateway. The network ID and join key in the device must match the network ID
and join key of the wireless gateway.
You may obtain the network ID and join key from the wireless gateway on the
Setup
→
Network
→
Setttings
page on the web interface. You may change the Network ID and Join
Joining the transmitter to a wireless network