Reference Manual
00809-0100-4860, Rev BF
Installation
May 2019
42
Rosemount 8600 Vortex Flow Meter
shows the indicator display with all segments lit.
A HART-based communicator can be used to change the engineering units of the
parameters displayed on the indicator. (See
3.7.1
Installing the indicator
For flowmeters ordered with the LCD indicator, the indicator is shipped installed. When
purchased separately from the Rosemount 8600D, you must install the indicator using a
small instrument screwdriver and the indicator kit (part number 8600-5640). The indicator
kit includes:
One LCD indicator assembly
One extended cover with o-ring installed
One connector
Two mounting screws
Two jumpers
, use the following steps to install the
LCD indicator:
1.
If the flowmeter is installed in a loop, secure the loop and disconnect the power.
2.
Remove the flowmeter cover on the electronics side.
Note
The circuit board is electrostatically sensitive. Be sure to observe handling precautions for
static-sensitive components.
3.
Insert the mounting screws into the LCD indicator.
4.
Remove the two jumpers on the circuit board that coincide with the Alarm and the
Security settings.
Figure 3
-
18. Optional Liquid Crystal Display