
Reference Manual
00809-0100-4860, Rev BF
Installation
May 2019
28
Rosemount 8600 Vortex Flow Meter
.
.
3.4.2
LCD indicator option
If your electronics are equipped with the LCD indicator (Option M5), the ALARM and
SECURITY jumpers are located on the face of the indicator as shown in
.
3.5
Meter body installation tasks
The installation tasks include detailed mechanical and electrical installation procedures.
3.5.1
Handling
Handle all parts carefully to prevent damage. Whenever possible, transport the system to
the installation site in the original shipping containers. Keep the shipping plugs in the
conduit connections until you are ready to connect and seal them.
Table 3
-
1. Analog Output: Standard Alarm Values vs. Saturation Values
Level
4—20 mA Saturation Value
4—20 mA Alarm Value
Low
3.9 mA
< 3.75 mA
High
20.8 mA
21.75 mA
Table 3
-
2. Analog Output: NAMUR-Compliant Alarm Values vs. Saturation Values
Level
4—20 mA Saturation Value
4—20 mA Alarm Value
Low
3.8 mA
< 3.6 mA
High
20.5 mA
22.6 mA
Figure 3
-
6. LCD Indicator Alarm and Security Jumpers
ALARM
LO
HI
OFF
ON
SECURITY