45
Reference Manual
00809-0100-4728, Rev MB
July 2016
3.4
Installation procedures
Figure 3-1. Installation Flowchart
3.4.1
Set the alarm switch
Make sure the alarm switch is set to the desired position before putting the device into operation to
ensure correct function in the instance of a failure.
Without an LCD display
1. Set the loop to manual (if applicable) and disconnect the power.
2. Remove the housing cover.
3. Set the physical hardware alarm switch to the desired position.
H
indicates High,
L
indicates Low.
Then reattach the housing cover. See
below for alarm switch location.
4. Apply power and set the loop to automatic control.
START
HERE
Bench
Calibration?
BASIC SETUP
Set Sensor Type
Set Number of Wires
Set Units
Set Range Values
Set Damping
VERIFY
Simulate Sensor Input
Within
Specifications?
FIELD INSTALL
Set Failure Mode Switch
Mount Transmitter
Wire Transmitter
Power Transmitter
FINISHED