29
Reference Manual
00809-0100-4728, Rev MB
Configuration
July 2016
Configuration
Table 2-5. Custom Alarm and Saturation Values
Note
Transmitters set to HART multidrop mode send all saturation and alarm information digitally; saturation
and alarm conditions will not affect the analog output.
Using with a Field Communicator
Using with AMS Device Manager
Right click on the device and select
Configure
.
1. In the left navigation pane choose
Manual Setup
.
2. On the
Analog Output
Tab find the Alarm and Saturation Levels group box.
3. Enter the High Alarm, High Saturation, Low Saturation and Low Alarm levels to the desired vales.
4. Click
Apply
when complete.
Usingh the Local Operator Interface
Reference the figure below to find the Alarm and Saturation value configuration path on the LOI.
Figure 2-16. Configuring Alarm and Saturation Values with LOI
* Available only if option code (S) is ordered.
** Available only if option Codes (S) and (DC) are both ordered.
Level
4–20 mA saturation
4–20 mA alarm
Low
3.7 mA - 3.9 mA
3.6 mA - 3.8 mA
High
20.1 mA - 22.9 mA
20.2 mA - 23.0 mA
From the
HOME
screen, enter the Fast Key sequence
Device Dashboard Fast Keys
2, 2, 5, 6
CALIBRAT
DAMPING
VARIABLE MAP
TAG
ALM SAT VALUES
ALM SAT VALUES
PASSWORD
SIMULATE
HART REV
HOT BACK CONFIG**
DRIFT ALERT**
....
ROSEMNT VALUES
NAMUR VALUES
OTHER VALUES
BACK TO MENU
EXIT MENU
VIEW CONFIG
SENSOR CONFIG
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXTENDED MENU
EXIT MENU
Summary of Contents for Rosemount 644 HART
Page 2: ......
Page 16: ...6 Reference Manual 00809 0100 4728 Rev MB Introduction July 2016 Introduction ...
Page 86: ...76 Reference Manual 00809 0100 4728 Rev MB Troubleshooting July 2016 Troubleshooting ...
Page 138: ...128 Reference Manual 00809 0100 4728 Rev MB Index July 2016 Index ...
Page 139: ......