11
Reference Manual
00809-0100-4728, Rev MB
Configuration
July 2016
Configuration
Turn on the Field Communicator by pressing the ON/OFF key. The Field Communicator will search for a
HART-compatible device and indicate when the connection is made. If the Field Communicator fails to
connect, it indicates that no device was found. If this occurs, refer to
Section 6: Troubleshooting
.
Figure 2-2. Field Communicator Device Dashboard Interface
Field Communicator menu trees and Fast Keys are available in
Appendix C: Field Communicator Menu
Trees and Fast Keys
Configuring with AMS Device Manager
With an AMS Device Manager software package, you can commission and configure instruments,
monitor status and alerts, troubleshoot from the control room, perform advanced diagnostics, manage
calibration, and automatically document activities with a single application.
Full configuration capability with AMS Device Manager requires loading the most current Device
Descriptor (DD) for this device. Download the latest DD at www.emersonprocess.com, or www.hart-
comm.org.
Note
All steps listed in this product manual using AMS Device Manager assume the use Version 11.5.
Configuring with a Local Operator Interface
The LOI requires option code M4 to be ordered. To activate the LOI push either configuration button.
Configuration buttons are located on the LCD display (must remove housing cover to access the
interface. See
Table 2-2
for configuration button functionality and
Figure 2-3
for configuration button
location. When using the LOI for configuration, several features require multiple screens for a successful
configuration. Data entered will be saved on a screen-by-screen basis; the LOI will indicate this by flashing
"SAVED" on the LCD display each time.
Note
Entering into the LOI menu effectively disables the ability to write to the device by any other host or
configuration tool. Make sure this is communicated to necessary personnel before using the LOI for
device configuration.
Summary of Contents for Rosemount 644 HART
Page 2: ......
Page 16: ...6 Reference Manual 00809 0100 4728 Rev MB Introduction July 2016 Introduction ...
Page 86: ...76 Reference Manual 00809 0100 4728 Rev MB Troubleshooting July 2016 Troubleshooting ...
Page 138: ...128 Reference Manual 00809 0100 4728 Rev MB Index July 2016 Index ...
Page 139: ......