Figure 2-15. Change in Input vs. Change in Output with Damping Set to 5 Seconds
Damping can be applied to a number of parameters in the Rosemount 644 Transmitter. Variables that
can be damped are:
Primary Variable (PV)
Sensor 1
Sensor 2
Differential Temperature
Average Temperature
1st Good Temperature
Note
The instructions below only refer to the damping of the Primary Variable (PV).
Using a Field Communicator
Using AMS Device Manager
Right click on the device and select
Configure
.
1. In the left navigation pane choose
Manual Setup
.
2. On the
Sensor 1
Tab find the Setup group box.
3. Change the
Damping Value
to the desired setting.
4. Click
Apply
when complete.
From the
HOME
screen, enter the Fast Key sequence
HART 5
HART 7
Device Dashboard Fast Keys
2, 2, 1, 5
2, 2, 1, 6